SOR 815PT Smart Pressure Transmitter User Manual
Page 7

Form 1571 (10.13) ©SOR Inc.
7/24
R
L
> 250
The table below contains a short description of the four 815PT device variables.
Device Definition Table
Variables
Value
Default Unit
Primary Variable (PV)
Pressure
PSI
Secondary Variable (SV)
Temperature
Degrees Celcius
Tertiary Variable (TV)
Loop voltage
Volts
Feduciary Variable (FV)
Dynamic
n/a
Under normal operating conditions, the analog output signal of the 815PT will remain
between 4mA and 20mA. In the event that the pressure goes beyond the normal
operating range of the device or in a fault condition, the 815PT will indicate the
condition on the 4-20 mA loop. The table below summarizes the 815PT loop current
with the associated fault indication.
Fault Current Indication
Loop Current
Description
3.6 mA
Fault Indication (Configurable: 3.6 mA or 21.0 mA)
3.8 mA
Low limit of output range
20.5 mA
High limit of output range
21.0 mA
Fault Indication (Configurable: 3.6 mA or 21.0 mA)
Device Variables and Fault Current Indicators
Confi guration with HART Communicator
4-20 mA Output