Troubleshooting

Symptom

Probable Cause

Float in actuated position but no output
signal.

 No power supply.
 Switch damaged. (Replace.)

Float in de-actuated position but still
receiving an output signal.

 Switch damaged. (Replace.)

Control will not function when installed
but operates when removed from pro-
cess connection.

 Inadequate float travel. Float travel
restricted by mounting nozzle. See
Mounting Requirements.

Liquid in vessel at the actuation level
but unit does not respond.

 Leaky or collapsed float. (Replace.)
 Liquid specific gravity too low.
 Float stem bound up or dirty. (Clean.)

Part Number

Description

3130-052

316SS Float Assembly

3130-091

W9 - SPST Hermetically Sealed Switch Capsule

3130-245

W1 - SPDT Hermetically Sealed Switch Capsule

3130-259

W1 - SPDT Switch/Conduit Connection Assembly (CK Option Only)

3130-107

L9 - SPST Hermetically Sealed Switch Capsule

3130-244

L1 - SPDT Hermetically Sealed Switch Capsule

3130-260

L1 - SPDT Switch/Conduit Connection Assembly (CK Option Only)

9227-028

MC Manual Check Assembly for 1 1/2” NPT Body*

9227-029

MD Manual Check Assembly for 1 1/2” NPT Body*

9227-024

MC Manual Check Assembly for 2” NPT Body*

9227-025

MD Manual Check Assembly for 2” NPT Body*

3130-040

20’ Remote Cable with two cable crimps, for use with MC or MD
accessory only.

Replacement Parts

* Unit must have originally been supplied with MC or MD option.