Chapter 5:

Channel Configuration, Data, and Status

49

.DigitalFilter

0- 32767 ms

INT

The time constant for a digital first order lag filter applied to the input data

for smoothing noise transients. 0 = no digital filter. 100 = data will

achieve 63.2% of its value in 100ms.