3-6
MicroLogix™ 1200 IO 8 Ch Output Module
User’s Manual Pub. 0300246-01 Rev. B
Table 3-3 (Data Words 1 through 4)
To Select
Channels 1, 3, 5, or 7
Channels 0, 2,4 or 6
15
14
13
12
11
10
9
8
7 6 5 4 3
2
1
0
Output
Type
4 to 20 mA
0 0
0
0
0
0
0 to 20 mA
0
0
1
0
0
1
-10 to 10 V
0
1
0
0
1
0
0 to 10 V
0
1
1
0
1
1
1 to 5 V
1
0
0
1
0
0
0 to 5 V
1
0
1
1
0
1
Reserved
1
1
0
1
1
0
Channel Disabled
1
1
1
1
1
1
Data
Format
Scaled for PID
0 0
0 0
Engineering Units
0 1 0 1
Percent Range
1 0 1 0
Raw/Proportional
Data
1 1 1 1
Unused
0 0 0 0 0 0