Table 10. Data format definitions

Selected

Data Value (counts)

Corresponding Signal

Data Format

Output Range

Min.

Max.

Min.

Max.

Engineering Units

±

10 V

-10250

+10250

-10.25 V

+10.25 V

0–10 V

-500

+10250

-0.50 V

+10.25 V

0–5 V

-500

+5500

-0.50 V

+5.50 V

1–5 V

+500

+5500

+0.50 V

+5.50 V

0–20 mA

0

+20500

0.0 mA

+20.5 mA

0–21 mA

0

+21500

0.0 mA

+21.5 mA

4–20 mA

+3500

+20500

+3.5 mA

+20.5 mA

Scaled for PID

±

10 V

0

+16383

-10 V

+10 V

0–10 V

0

+16383

0 V

+10 V

0–5 V

0

+16383

0 V

+5 V

1–5 V

0

+16383

+1 V

+5 V

0–20 mA

0

+16383

0 mA

+20 mA

0–21 mA

0

+16383

0 mA

+21 mA

4–20 mA

0

+16383

+4 mA

+20 mA

Proportional Counts

±

10 V

-32768

+32767

-10.25 V

+10.25 V

0–10 V

-32768

+32767

-0.50 V

+10.25 V

0–5 V

-32768

+32767

-0.50 V

+5.50 V

1–5 V

-32768

+32767

+0.50 V

+5.50 V

0–20 mA

-32768

+32767

0.0 mA

+20.5 mA

0–21 mA

-32768

+32767

0.0 mA

+21.5 mA

4–20 mA

-32768

+32767

+3.5 mA

+20.5 mA

1746-NO4-

±

10 V

-32768

+32767

-10 V

+10 V

Compatible

①

0–10 V

0

+32767

0 V

+10 V

0–5 V

0

+16384

0 V

+5 V

1–5 V

+3277

+16384

+1 V

+5 V

0–20 mA

0

+31208

0 mA

+20 mA

0–21 mA

0

+32767

0 mA

+21 mA

4–20 mA

+6242

+31208

+4 mA

+20 mA

User-Defined

±

10 V

-10.25 V

+10.25 V

Scale

0–10 V

-0.50 V

+10.25 V

0–5 V

-0.50 V

+5.50 V

1–5 V

See note

➁

+0.50 V

+5.50 V

0–20 mA

0.0 mA

+20.5 mA

0–21 mA

0.0 mA

+21.5 mA

4–20 mA

+3.5 mA

+20.5 mA

①

Provides direct compatibility with the 1746-NO4 module.

➁

For the user-defined scale, the data in output words 6 and 7 determine the count limits.

See the next subsection,