Defender series surge + pdu user manual, Ix. specifications, Surgex rev-c page 6 – SurgeX Defender Series Surge + PDU User Manual
Page 6

Defender Series Surge + PDU User Manual
© SurgeX
REV-C
Page 6
IX.
Specifications
SX-DS-L630-FP
SX-DS-L530-FP
SX-DS-520-FP
SX-DS-IEC-FP
Voltage Rating
120/230 Volts Split Phase
120 Volts Single Phase
120 Volts Single Phase
230 Volts Single Phase
Frequency
50/60 Hz
50/60 Hz
50/60 Hz
50/60 Hz
Load Rating
24 Amp Maximum Capacity
24 Amp Maximum Capacity
20 Amp Maximum Capacity
30 Amp Maximum Capacity
Input Connector
NEMA L6-30P
NEMA L5-30P
NEMA 5-20P
IEC-60309 332P65
Output Connector
(6) IEC-320 C13
(6) IEC-320 C13
(6) IEC-320 C13
(6) IEC-320 C13
Overload Protection (2) Circuit Breaker
(2) Circuit Breaker
(2) Circuit Breaker
(3) Circuit Breaker
Voltage Protection
Rating (VPR)
800V Line - Line
500V Line - Ground
330V All Modes
330V All Modes
800V Line - Line
500V Line - Ground
Power Requirement
(no load)
8 Watts
8 Watts
8 Watts
8 Watts
Attenuation
Normal Mode:
>30dB 50kHz - 50MHz
Common Mode:
>30dB 150kHz - 50MHz
Normal Mode:
>30dB 50kHz - 50MHz
Common Mode:
>30dB 50kHz - 50MHz
Normal Mode:
>30dB 50kHz – 50MHz
Common Mode:
>30dB 50kHz – 50MHz
Normal Mode:
>30dB 50kHz - 50MHz
Common Mode:
>30dB 150kHz - 50MHz
Over-Voltage
Shutdown
280 Volts (±2%)
Restores at 260 Volts (±2%)
150 Volts (±2%)
Restores at 135 Volts (±2%)
150 Volts (±2%)
Restores at 135 Volts (±2%)
280 Volts (±2%)
Restores at 260 Volts (±2%)
Response Time
100 msec Over-Voltage
100 msec Over-Voltage
100 msec Over-Voltage
100 msec Over-Voltage
Dimensions
17.44” W x 12.08” D x 1.71” H
(1 RU)
17.44” W x 12.08” D x 1.71” H
(1 RU)
17.44” W x 12.08” D x 1.71”
H
(1 RU)
17.44” W x 12.08” D x 1.71” H
(1 RU)
Weight
12.5 lb
12.5 lb
12.5 lb
12.5 lb
Input Cord Length
3 m
3 m
3 m
3 m
Rack Mounting
Hardware
Included
Included
Included
Included
Standalone
Hardware
Included
Included
Included
Included
Power Indicator
LED (Green)
LED (Green)
LED (Green)
LED (Green)
Wiring Fault
Indicator
LED (Red) Illuminated when
no protective Earth Ground
present
LED (Red) Illuminated when
no protective Earth Ground
present or when Line/Neutral
reversed
LED (Red) Illuminated when
no protective Earth Ground
present or when Line/Neutral
reversed
LED (Red) Illuminated when
no protective Earth Ground
present
BTU/h
100 BTU/h Maximum at full
rated load
100 BTU/h Maximum at full
rated load
100 BTU/h Maximum at full
rated load
140 BTU/h Maximum at full
rated load
Temperature Range
5°C to 40°C
5°C to 40°C
5°C to 40°C
5°C to 40°C
Humidity Range
5% to 95% R.H. Non-
condensing
5% to 95% R.H. Non-
condensing
5% to 95% R.H. Non-
condensing
5% to 95% R.H. Non-
condensing
Agency Listings
TUV Certified to UL 60950-1
Check surgex.com/
defenderseries for country
specific certifications
TUV Certified to UL 60950-1
Check surgex.com/
defenderseries for country
specific certifications
TUV Certified to UL 60950-1
Check surgex.com/
defenderseries for country
specific certifications
CE/CB
Check surgex.com/
defenderseries for country
specific certifications
Specifications subject to change without notice
All listed specifications obtained at an ambient temperature of 25°