Installation, Continued, Floor clearances – Desa VYM27NRPR User Manual

Page 9: Mantel clearances, Determining minimum mantel clearance

Advertising
background image

110398-01A

For more information, visit www.desatech.com

For more information, visit www.desatech.com

9

9

INSTALLATION

Continued

FLOOR CLEARANCES

A. If installing appliance on the floor level, you must maintain

the minimum distance of 14" to combustibles (see Figure 8).

B. If combustible materials are less than 14" to the fireplace, you

must install appliance at least 5" above the combustible floor-
ing (see Figure 9).

NOTICE: If your installation does not meet the mini-
mum clearances shown, you must do one of the
following:
• operate the logs only with the flue damper open
• raise the mantel to an acceptable height
• remove the mantel

NOTICE: Surface temperatures of adjacent walls and
mantels become hot during operation. Walls and
mantels above the firebox may become hot to the
touch. If installed properly, these temperatures meet
the requirement of the national product standard.
Follow all minimum clearances shown in this manual.

Figure 7 - Minimum Mantel Clearances When Using Hood

Figure 6 - Minimum Mantel Clearances Without Using Hood

Minimum Non-
Combustible
Material

Minimum Non-
Combustible
Material Height

Distances to
Underside of
Mantel

Top of Fireplace
Opening

Underside of
Mantel Shelf

Mantel Shelf

12"

(A)

18"

20"

22"

24"

All minimum
distances are
in inches

2

1

/2

"

6"

8"

10"

Minimum Non-
Combustible
Material

8"
Min.

12"

15"

18"

All minimum
distances are
in inches

20"

2

1

/2

"

6"

8"

10"

12"

Distances to
Underside of
Mantel

Hood
(GA6050, GA6052)

Top of Fireplace
Opening

Underside of
Mantel Shelf

Mantel Shelf

Figure 8 - Minimum Fireplace Clearances If Installed at Floor
Level

Figure 9 - Minimum Fireplace Clearances Above Combustible
Flooring

14"
Min.

Combustible
Material

Non-Combustible Material

Hearth

5"
Min.

Combustible
Material

Hearth

Combustible
Material

5”
Min.

Hood (GA6050,
GA6052 or GA6053)

MANTEL CLEARANCES

In addition to meeting noncombustible material clearances, you
must also meet required clearances between fireplace openings and
mantel shelf on each side of the fireplace. If you do not meet the
clearances listed in this section, you will need a hood.

Determining Minimum Mantel Clearance

If you meet minimum clearance between mantel shelf and top of
fireplace opening, a hood is not required (see Figure 6).

Determining Minimum Mantel Clearance When
using a Hood

If minimum clearances in Figure 6 are not met, you must have a
hood. When using a hood there are still certain minimum mantel
clearances required. Follow minimum clearances shown in Figure
7 when using hood.

INSTALLATION

Mantel Clearances

Floor Clearances

Advertising