DOD PS-7 User Manual

Page 6

Advertising
background image

(4) Change the value by using the UP/DOWN switches (“U” or “V”). When you are done, press the special

command switch again, and the alternating display in the bottom right corner of the LCD display will

become constant. The process is now finished.

Default value

LCD

Screen

Indication

The function

to be set

Remarks

Toxic:

CDS-7

Combustible

: CHS-7

Oxygen:

COS-7

Adjustable

Range

d1 **

Time delay 1

Time delay (secs.) of the gas
alarm contact (1st level)

d1 0

d1 0

0 to 99 sec

d2 **

Time delay 2

Time delay (secs.) of the gas
alarm contact (2nd level)

d2 0

d2 0

0 to 99 sec

az

Analog output
(base)

(*For our maintenance purposes only)

as

Analog output
(span)

(*For our maintenance purposes only)

zs *

Zero
suppression, or
21vol%
suppression

Displays the percentage of the full
scale value (rounded to the
percent)

zs 5

zs 2

0 to 30%

H-H
L-L
H-L

Alarm mode

1st: upper limit, 2nd : upper limit
warning
1st : lower limit, 2nd : lower limit
warning
1st : upper limit, 2nd: lower limit
warning

H-H L-L

H-H

L-L

H-L

Con *

Pyroletic
converter
failure alarm

: Off 1: On

Con 0

Con 0

0

or

1

CG **

Calibration
gas
concentration

(*For our maintenance purposes only)

CG 40

CG 84

nEt *

The existence
of a DeviceNet
unit

: Non-existent 1: Existent nEt 0

nEt 0

0

or

1

F ***

Display off
value

Calibration gas type in lower right of
LCD
f value in center of LCD

(Depending on the sensor unit)

FL ***

Displays rate
of flow

Shows the current rate of flow
(mL/min)

(Depending on the rate of flow)

P ***

Sensor unit
output

(*For our maintenance purposes)

--

At *

Auto 21vol%
adjustment

: Off 1: On

--

A t 1

0

or

1

Each

time
the UP

swit

ch

is

press

ed,

it

wi
ll move

dow

n t

he t
abl
e

to

the nex

t it

em.

When t

he
D

O

WN sw

itc

h

is

press

ed,
it

w

ill

mov

e

u

p

on

e.

×××

Type of sensor unit (Normal display)

(Depending on the sensor unit)

Advertising