Flush fixing surface fixing, 2 two channel, individual switches, 3 two channel, common switch – CP Electronics EBDSPIR-DD-LV User Manual

Page 4: 4 single channel switching

Advertising
background image

page 4

FLUSH FIXING

SURFACE FIXING

1

2

2

1

Hole Ø64mm

Warning - be careful
bending springs when
mounting unit.

Pull out spring tab and rotate
spring arm as shown

50mm or 60mm fixing centres

page 9

6.2 Two channel, individual switches


Functions:
Switches both channels with occupancy. Maintains illuminance, dims and switches the
dimming channel using optional single position retractive switch (switch 2). Switches the switching channel
using the optional single position retractive switch (switch 1).

Configured to presence detection: Turns on automatically with occupancy. Maintains illuminance
(dimming channel only). Press and release switch to toggle output. Press and hold switch to dim up and
down (reverses direction with each press). Turns off after occupancy.

Configured to absence detection: Press and release switch to turn on. Maintains illuminance (dimming
channel only). Press and release switch to turn off. Press and hold switch to dim up and down (reverses
direction with each press). Turns off after occupancy.

Channel mode: Set to ―Switch and dim separate‖

Switch mode:
Set to ―1 position switch separate‖

6.3 Two channel, common switch


Functions:
Switches both channels with occupancy. Maintains illuminance, dims and switches the
dimming channel using optional centre biased retractive switch .
Configured to presence detection: Turns on automatically with occupancy. Maintains illuminance
(dimming channel only). Press and release down switch to turn off. Press and release up switch to turn
back on. Press and hold up switch to dim up, press and hold down switch to dim down. Turns off after
occupancy. Channel 1 does not operate with switch.
Configured to absence detection:
Press and release up switch to turn on. Maintains illuminance
(dimming channel only). Press and release down switch to turn off. Press and hold up switch to dim up,
press and hold down switch to dim down. Turns off after occupancy. Channel 1 does not operate with
switch.
Channel mode: Set to ―Switch and dim separate‖
Switch mode: Set to ―2 position switch separate‖

OPTION 1(B): USING A CENTRE BIASED RETRACTIVE SWITCH TO PROVIDE
ABSENCE DETECTION, WILL ALSO PROVIDE OPTIONAL OVERRIDE OFF.

OPTION 2: USING A CENTRE BIASED RETRACTIVE SWITCH TO PROVIDE
SWITCHED AND DIMMING OUTPUT (STANDARD CONFIGURATION)

OPTION 3(A): USING 2 MOMENTARY PUSH TO MAKE SWITCHES TO PROVIDE SWITCHED OUTPUT TO A
NON-DIMMING LUMINAIRE AND SWITCHED / DIMMING OUTPUT TO A DIMMING LUMINAIRE OVER 2 CHANNELS

OPTION 3(B): USING A CENTRE BIASED RETRACTIVE SWITCH TO PROVIDE SWITCHED OUTPUT TO A
NON-DIMMING LUMINAIRE AND SWITCHED / DIMMING OUTPUT TO A DIMMING LUMINAIRE OVER 2 CHANNELS

6.2 Two Channel, individual switches

6.3 Two Channel, common switch

6.1 Single channel dimming

+

EBDSPIR-DD-LV SENSOR

SW1/UP

DIM+

DIM-

SW2

DOWN

DIMMING

BALLAST

DIMMING LUMINAIRE

(DSI or DALI)

CENTRE BIASED

RETRACTIVE SWITCH

Optional for presence,

mandatory for absence detection

6.4 Single channel switching

+

EBDSPIR-DD-LV SENSOR

SW1/UP

DIM+

DIM-

SW2

DOWN

CENTRE BIASED

RETRACTIVE SWITCH

Optional for presence,

mandatory for absence detection

+

EBDSPIR-DD-LV SENSOR

SW1/UP

DIM+

DIM-

SW2

DOWN

DIMMING

BALLAST

DIMMING LUMINAIRE

(DSI or DALI)

CENTRE BIASED

RETRACTIVE SWITCH

Optional for presence,

mandatory for absence detection

+

EBDSPIR-DD-LV SENSOR

SW1/UP

DIM+

DIM-

SW2

DOWN

DIMMING

BALLAST

DIMMING LUMINAIRE

(DSI or DALI)

SWITCH 1 - MOMENTARY

PUSH TO MAKE SWITCH

Optional for presence,

mandatory for absence detection

SWITCH 2 - MOMENTARY

PUSH TO MAKE SWITCH

Optional for presence,

mandatory for absence detection

OUT

+

COM

LOAD

INTERNAL

RELAY

LOAD CONNECTIONS
-DD-LV
-DD-LV/GOLD

OUT

+

COM

INTERNAL OPEN

COLLECTOR

TRANSISTOR

LOAD CONNECTIONS
-DD-LV/OC

LOAD

OUT

COM

AC Supply

10VAC - 26.5VAC

DC Supply

11.5VDC - 36VDC

OR

-

+

OUT

COM

AC Supply

10VAC - 26.5VAC

DC Supply

11.5VDC - 36VDC

OR

-

+

INPUT & SWITCH
CONNECTIONS

OUT

COM

AC Supply

10VAC - 26.5VAC

DC Supply

11.5VDC - 36VDC

OR

-

+

INPUT & SWITCH
CONNECTIONS

OUT

COM

AC Supply

10VAC - 26.5VAC

DC Supply

11.5VDC - 36VDC

OR

-

+

INPUT & SWITCH
CONNECTIONS

OUT

+

COM

LOAD

INTERNAL

RELAY

LOAD CONNECTIONS
-DD-LV
-DD-LV/GOLD

OUT

+

COM

INTERNAL OPEN

COLLECTOR

TRANSISTOR

LOAD CONNECTIONS
-DD-LV/OC

LOAD

OUT

+

COM

LOAD

INTERNAL

RELAY

LOAD CONNECTIONS
-DD-LV
-DD-LV/GOLD

OUT

+

COM

INTERNAL OPEN

COLLECTOR

TRANSISTOR

LOAD CONNECTIONS
-DD-LV/OC

LOAD

Advertising