Flush fixing surface fixing, 2 two channel, individual switches, 3 two channel, common switch – CP Electronics EBDSPIR-DD-LV User Manual
Page 4: 4 single channel switching

page 4
FLUSH FIXING
SURFACE FIXING
1
2
2
1
Hole Ø64mm
Warning - be careful
bending springs when
mounting unit.
Pull out spring tab and rotate
spring arm as shown
50mm or 60mm fixing centres
page 9
6.2 Two channel, individual switches
Functions: Switches both channels with occupancy. Maintains illuminance, dims and switches the
dimming channel using optional single position retractive switch (switch 2). Switches the switching channel
using the optional single position retractive switch (switch 1).
Configured to presence detection: Turns on automatically with occupancy. Maintains illuminance
(dimming channel only). Press and release switch to toggle output. Press and hold switch to dim up and
down (reverses direction with each press). Turns off after occupancy.
Configured to absence detection: Press and release switch to turn on. Maintains illuminance (dimming
channel only). Press and release switch to turn off. Press and hold switch to dim up and down (reverses
direction with each press). Turns off after occupancy.
Channel mode: Set to ―Switch and dim separate‖
Switch mode: Set to ―1 position switch separate‖
6.3 Two channel, common switch
Functions: Switches both channels with occupancy. Maintains illuminance, dims and switches the
dimming channel using optional centre biased retractive switch .
Configured to presence detection: Turns on automatically with occupancy. Maintains illuminance
(dimming channel only). Press and release down switch to turn off. Press and release up switch to turn
back on. Press and hold up switch to dim up, press and hold down switch to dim down. Turns off after
occupancy. Channel 1 does not operate with switch.
Configured to absence detection: Press and release up switch to turn on. Maintains illuminance
(dimming channel only). Press and release down switch to turn off. Press and hold up switch to dim up,
press and hold down switch to dim down. Turns off after occupancy. Channel 1 does not operate with
switch.
Channel mode: Set to ―Switch and dim separate‖
Switch mode: Set to ―2 position switch separate‖
OPTION 1(B): USING A CENTRE BIASED RETRACTIVE SWITCH TO PROVIDE
ABSENCE DETECTION, WILL ALSO PROVIDE OPTIONAL OVERRIDE OFF.
OPTION 2: USING A CENTRE BIASED RETRACTIVE SWITCH TO PROVIDE
SWITCHED AND DIMMING OUTPUT (STANDARD CONFIGURATION)
OPTION 3(A): USING 2 MOMENTARY PUSH TO MAKE SWITCHES TO PROVIDE SWITCHED OUTPUT TO A
NON-DIMMING LUMINAIRE AND SWITCHED / DIMMING OUTPUT TO A DIMMING LUMINAIRE OVER 2 CHANNELS
OPTION 3(B): USING A CENTRE BIASED RETRACTIVE SWITCH TO PROVIDE SWITCHED OUTPUT TO A
NON-DIMMING LUMINAIRE AND SWITCHED / DIMMING OUTPUT TO A DIMMING LUMINAIRE OVER 2 CHANNELS
6.2 Two Channel, individual switches
6.3 Two Channel, common switch
6.1 Single channel dimming
+
EBDSPIR-DD-LV SENSOR
SW1/UP
DIM+
DIM-
SW2
DOWN
DIMMING
BALLAST
DIMMING LUMINAIRE
(DSI or DALI)
CENTRE BIASED
RETRACTIVE SWITCH
Optional for presence,
mandatory for absence detection
6.4 Single channel switching
+
EBDSPIR-DD-LV SENSOR
SW1/UP
DIM+
DIM-
SW2
DOWN
CENTRE BIASED
RETRACTIVE SWITCH
Optional for presence,
mandatory for absence detection
+
EBDSPIR-DD-LV SENSOR
SW1/UP
DIM+
DIM-
SW2
DOWN
DIMMING
BALLAST
DIMMING LUMINAIRE
(DSI or DALI)
CENTRE BIASED
RETRACTIVE SWITCH
Optional for presence,
mandatory for absence detection
+
EBDSPIR-DD-LV SENSOR
SW1/UP
DIM+
DIM-
SW2
DOWN
DIMMING
BALLAST
DIMMING LUMINAIRE
(DSI or DALI)
SWITCH 1 - MOMENTARY
PUSH TO MAKE SWITCH
Optional for presence,
mandatory for absence detection
SWITCH 2 - MOMENTARY
PUSH TO MAKE SWITCH
Optional for presence,
mandatory for absence detection
OUT
+
COM
LOAD
INTERNAL
RELAY
LOAD CONNECTIONS
-DD-LV
-DD-LV/GOLD
OUT
+
COM
INTERNAL OPEN
COLLECTOR
TRANSISTOR
LOAD CONNECTIONS
-DD-LV/OC
LOAD
OUT
COM
AC Supply
10VAC - 26.5VAC
DC Supply
11.5VDC - 36VDC
OR
-
+
OUT
COM
AC Supply
10VAC - 26.5VAC
DC Supply
11.5VDC - 36VDC
OR
-
+
INPUT & SWITCH
CONNECTIONS
OUT
COM
AC Supply
10VAC - 26.5VAC
DC Supply
11.5VDC - 36VDC
OR
-
+
INPUT & SWITCH
CONNECTIONS
OUT
COM
AC Supply
10VAC - 26.5VAC
DC Supply
11.5VDC - 36VDC
OR
-
+
INPUT & SWITCH
CONNECTIONS
OUT
+
COM
LOAD
INTERNAL
RELAY
LOAD CONNECTIONS
-DD-LV
-DD-LV/GOLD
OUT
+
COM
INTERNAL OPEN
COLLECTOR
TRANSISTOR
LOAD CONNECTIONS
-DD-LV/OC
LOAD
OUT
+
COM
LOAD
INTERNAL
RELAY
LOAD CONNECTIONS
-DD-LV
-DD-LV/GOLD
OUT
+
COM
INTERNAL OPEN
COLLECTOR
TRANSISTOR
LOAD CONNECTIONS
-DD-LV/OC
LOAD