24

Installation

Emotron AB 01-2120-01r2

Fig. 12 Type of Auto set

NOTE: See note on page 22.

Power

A3

A1

A2

B2

B1

B3

Time

When there is liquid in the pit
A1=Motor load when the pump does not snore (window 13 is set to (¯)).
A2=Stop level if Auto set is pressed when the pump does not snore (window 11).
A3=Snore margin (window 12).

When there is NO liquid in the pit
B1=Motor load when the pump is snoring/dry pumping (window 13 is set to (_)).
B2=Stop level if Auto set is pressed when the pump is snoring/dry pumping (window 11).
B3= Snore margin (window 12).