CommLink IV Technical Guide

16

Operator Interface

Troubleshooting the USB Drivers

Troubleshooting Tips

Problems with Prism Software

Verify that the correct COM port, created by the USB

connection, is selected in the Job Site Window. Verify
COM port number in

<Control Panel>

,

<System>

,

<Hardware>

,

<Device Managers>

,

<Ports>

.

If using Prism II, verify that CommLink 4 is selected

for Type of CommLink in the Job Sites Window.

If using Prism, verify that the Baud Rate is set to 19200

in

the

Job Sites Window.

Verify that the correct CommLink mode is selected

under Network Confi guration in the Job Sites Window.

Verify that the USB switch on the back of the

CommLink is set to Normal.

Problems with USB Connection

Verify that the RX-USB and TX-USB are blinking

when you perform a Search for Units or try to open a
status screen in Prism.

If the USB LEDs fail to blink, disconnect and

reconnect the USB connection.

If the problem persists, verify that the USB drivers

have been installed properly.

Problems Viewing Controllers on a Network

Make sure that the CommLink communication dip

switch is set to Multi.

Make sure that in Prism, the CommLink fi eld in the Job

Sites

Window is set to zero for multiple loop.

In Prism II, make sure that Multiple Loop

Confi guration is selected for Network Confi guration in

the Job Sites Window.

NOTE:

WattMaster Controls Technical Support cannot trouble-
shoot internal PC and/or Windows-based operating
system problems.

NOTE:

WattMaster Controls Technical Support cannot trouble-

shoot fi rewalls, routers and/or problems on a customer’s
internal or external network. An IT professional may need
to be consulted.