Installation – Avalon Firestyles 864 HO GS2 Installation User Manual
Page 21

Installation
(for qualified installers only)
21
© Travis Industries
4140922
100-01410
Vent Configuration: Horizontal Termination (no vertical rise)
NOTE: A Wall thimble (part #58DVA-WT) is required.
The termination must fall within the shaded area shown in the chart. Use the indicated restrictor
positions.
NOTE: When venting horizontally, use minimum vent kit “C” (
96200316). If venting from a corner
installation, an additional 45° elbow is required.
45 Elbow
Termination
3 feet (0.915m)
0 feet
0 feet
4’ max (1.22m)
Exhaust Restrictor # 1 (stock)
Intake Restrictor # 1 (stock)
Vent with No 45˚ Elbow
3 feet (0.915m)
0 feet
0 feet
2
’ max (0.61m)
Vent with 1 45˚ Elbow
Min. 6" (152mm) Horizontal Section
Max. 24" (610mm) Horizontal Section(s)
Min. 6" (152mm) Horizontal Section
Max.48" (1219mm) Horizontal Section(s)
Exhaust Restrictor # 1 (stock)
Intake Restrictor # 1 (stock)
Optional 45 Elbow