Installation, Termination requirements – Avalon Firestyles 564 HO GS2 Installation User Manual

Page 30

Advertising
background image

30

Installation

(

for qualified installers only)

30

Travis Industries

4150330

100-01408

Termination Requirements

!

Venting terminals shall not be recessed into a wall or siding.

A

Minimum 9" (229mm) clearance from any door or window

B

Minimum 12" (305mm) above any grade, veranda, porch, deck or balcony

C

Minimum 1" (25mm) from outside corner walls
NOTE: Clearance in accordance with local installation codes and the requirements
of the gas supplier.

D

Minimum 1" (25mm) from inside corner walls
NOTE: Clearance in accordance with local installation codes and the requirements
of the gas supplier.

E

Minimum 11" (279mm) clearance below unventilated soffits or roof surfaces.
Minimum 18" (457mm) clearance below ventilated soffits.
Minimum 6" (152mm) clearance below roof eaves.
NOTE: Vinyl surfaces require 24" (610mm)
NOTE: Clearance in accordance with local installation codes and the requirements of the gas supplier.

F

Minimum 12" (305mm) clearance below a veranda, porch, deck or balcony.
NOTE: Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor.
NOTE: Clearance in accordance with local installation codes and the requirements of the gas supplier.

G

Minimum 48" (1219mm) clearance from any adjacent building.

H

Minimum 84" (2134mm) clearance above any grade when adjacent to public walkways or driveways.
NOTE: may not be used over a walkway or driveway shared by an adjacent building.

I

Minimum 9" (229mm) clearance to any non-mechanical air supply inlet to the building or the combustion air inlet
to any other appliance.

J

Minimum 36" (914mm) clearance above any mechanical air supply inlet if within 10’ (3M) horizontally.

K

Minimum 36" (914mm) from the area above the meter/regulator (vent outlet) - this extends 15’ (4.5M) above the regulator
NOTE: Clearance in accordance with local installation codes and the requirements of the gas supplier.

L

Minimum 36" (914mm) from the meter/regulator (vent outlet).
NOTE: Clearance in accordance with local installation codes and the requirements of the gas supplier.

M Minimum 12” (305mm) above the roof line (for vertical terminations).

N

Minimum 24” (610mm) horizontal clearance to any surface (such as an exterior wall) – for vertical terminations.

•

Use the vinyl siding standoff when installing on an exterior with vinyl siding.

•

Vent termination must not be located where it will become plugged by snow or other material

11" Min.

(279mm)

6" Min.
(152mm)

Roof
Surface

Roof
Eaves

C

B

H

E

G

A

D

F

L

K

J

I

NOTE: Measure clearances to the nearest edge of the exhaust hood.