Installation, Fireplace placement requirements – Avalon Firestyles DVL Fireplace EF-2003 to 2007 User Manual

Page 8

Advertising
background image

8

Installation

(for qualified installers only)

Travis Industries

4041206

1 0 0 - 0 1 1 4 7

Fireplace Placement Requirements

Minimum Framing Dimensions

A 1" clearance is required along the sides and back of the fireplace. The 1" stand-offs on the sides
and 6-3/8" stand-offs on the top of the fireplace are designed to separate the fireplace from the
framing members. These stand-offs may contact the framing members but no material may be placed
between the stand-offs.

54-3/4" Min.

44-1/4"

20-1/2"

46-3/4"

3" Clearance Min. Above Vent

The center of the vent is a
minimum 47-3/4" above the
base of the fireplace.

1" Clearance Min. to
the Sides of Vent

The fireplace enclosure
must not be less than
54-3/4" above the base
of the fireplace.

1" Clearance Min.
Below Vent

•

Fireplace must be installed on a level surface capable of supporting the fireplace and vent

•

Fireplace must be placed directly on wood or non-combustible surface (not on linoleum or carpet)

•

This heater may be placed in a bedroom. Please be aware of the large amount of heat this appliance
produces when determining a location.

Clearances

•

When installed, walls in front of the fireplace must be a minimum 6" to the side of the faceplate.

•

Due to the high temperature of the fireplace, it should be located out of traffic and away from furniture
and draperies.

•

Fireplace must be placed so the vents below and above the glass do not become blocked