Checking gas connections, Connecting to gas supply, Warning – Desa CGP18B User Manual

Page 15: Caution

Advertising
background image

15

100098

Figure 13 - Gas Connection

* An A.G.A. design certified manual shutoff valve with 1/8" NPT tap is an acceptable
alternative to test gauge connection. Purchase the optional A.G.A. design certified
manual shutoff valve from your dealer. See Accessories, page 27.

CHECKING

GAS

CONNECTIONS

Continued

IMPORTANT:

Hold pressure regulator with wrench when connecting it to gas piping

and/or fittings.

Tee Joint

Reducer
Bushing to
1/8" NPT

1/8" NPT
Plug Tap

Test

Gauge

Connection *

Tee Joint

Pipe

Nipple

Cap

Note:

Burner bracket

not shown for clarity

Heater
Cabinet

Pressure
Regulator

1/2" NPT
Pipe Nipple

Ground Joint
Union

Manual
Shutoff
Valve *

From

External

Regulator

(11" W.C. to 14" W.C. Pressure)

3" Minimum

Sediment

Trap

CONNECTING

TO GAS

SUPPLY

Continued

WARNING ICON

G 001

WARNING

Test all gas piping and connections for leaks after installing or
servicing. Correct all leaks at once.

WARNING ICON

G 001

WARNING

Never use an open flame to check for a leak. Apply a mixture of
liquid soap and water to all joints. Bubbles forming show a leak.
Correct all leaks at once.

WARNING ICON

G 001

CAUTION

Make sure external regulator has been installed between propane
supply and heater. See guidelines under

Connecting to Gas Sup-

ply, page 14.

PRESSURE TESTING GAS SUPPLY PIPING SYSTEM

Test Pressures In Excess Of 1/2 PSIG

1. Disconnect heater and its individual manual shutoff valve from gas supply

piping system. Pressures in excess of 1/2 PSIG will damage heater regulator.

2. Cap off open end of gas pipe where manual shutoff valve was connected.

Advertising