Analog output status points and control blocks – Basler Electric BE1-11 DNP3 Protocol User Manual
Page 75

9424200773 Rev A
69
Point
Index
Description
Change Event Default
Assigned Class
687
Motor Maintenance Data - Max RTD Group 3
(BE1-11m only)
2
688
Motor Maintenance Data - Max RTD Group 4
(BE1-11m only)
2
689-738
Reserved
739
Phase Differential Meter 1 Iop 2
nd
A
(BE1-11t only)
2
740
Phase Differential Meter 1 Iop 2
nd
B
(BE1-11t only)
2
741
Phase Differential Meter 1 Iop 2
nd
C
(BE1-11t only)
2
742
Phase Differential Meter 1 Iop 5
th
A
(BE1-11t only)
2
743
Phase Differential Meter 1 Iop 5
th
B
(BE1-11t only)
2
744
Phase Differential Meter 1 Iop 5
th
C
(BE1-11t only)
2
745
Fault Report – Days Since January 1, 1984
1
746
Fault Report – Milliseconds of Day
1
747
Active Settings Group
1
Analog Output Status Points and Control Blocks
Table 6 lists both the Analog Status Points (Object 40) and the Analog Output Control Blocks (Object 41).
It is important to note that Analog Output Status Points are not included into Class 0.
The Return Status Value for object 41 for all control operations may be 6 (hardware problem) due to a
value out of range, or a BE1-11 internal state. One of the reasons for rejection may be if another
communication port or front panel interface has access higher than READ. For more information, see the
appropriate BE1-11 instructional manual.
Each Analog Output Status Point has a setting for scaling factor configurable via BESTCOMSPlus.
Table 6. Analog Output Status Points and Control Blocks
Analog Output Status Points
Object Number: 40
Variations Supported: 1, 2, 3
Request Function Codes supported: 1 (read)
Default Variation Reported When Variation 0 Requested: 2 (16-Bit Analog Output Status)
Analog Output Blocks
Object Number: 41
Variations Supported: 1, 2, 3
Request Function Codes supported: 3 (select), 4 (operate), 5 (direct operate), 6 (direct operate, noack)
BE1-11
Point List