Group setting parameters, Global setting parameters – Basler Electric BE1-851 Modbus Protocol User Manual
Page 23

9289900992 Rev F
BE1-851 Modbus
™ Protocol
2-3
Holding
Read/Write
Data
Register Parameter
Supported
Format
Notes
40147
Select Output 4
R W
ASC(1)
40148
Operate Output 4
R W
ASC(1)
40149
Select Output 5
R W
ASC(1)
40150
Operate Output 5
R W
ASC(1)
∗ 243 and 343 are not available when style option 1 is V or W.
Group Setting Parameters
40269-70
50TP Pickup
R W
FP
GRP
40271-72
50TP Time Delay
R W
LI
GRP
40273-74
50TN Pickup
R W
FP
GRP
40275-76
50TN Time Delay
R W
LI
GRP
40277-78
50TQ Pickup (250TN, Sensing input “G”)
R W
FP
GRP
40279-80
50TQ Time Delay (250TN, Sensing input “G”)
R W
LI
GRP
40281-82
150TP Pickup
R W
FP
GRP
40283-84
150TP Time Delay
R W
LI
GRP
40285-86
150TN Pickup
R W
FP
GRP
40287-88
150TN Time Delay
R W
LI
GRP
40289-90
150TQ Pickup (350TN, Sensing input “G”)
R W
FP
GRP
40291-92
150TQ Time Delay (350TN, Sensing input “G”)
R W
LI
GRP
40305-06
51P Pickup
R W
FP
GRP
40307-08
51P Time Dial
R W
FP
GRP
40309-10
51P Curve Type
R W
ASC(3)
GRP
40311-12
51N Pickup
R W
FP
GRP
40313-14
51N Time Dial
R W
FP
GRP
40315-16
51N Curve Type
R W
ASC(3)
GRP
40317-18
51Q Pickup (151N, Sensing input “G”)
R W
FP
GRP
40319-20
51Q Time Dial (151N, Sensing input “G”)
R W
FP
GRP
40321-22
51Q Curve Type (151N, Sensing input “G”)
R W
ASC(3)
GRP
40359-60
62 Time Delay 1
R W
LI
GRP
40361-62
62 Time Delay 2
R W
LI
GRP
40363-64
162 Time Delay 1
R W
LI
GRP
40365-66
162 Time Delay 2
R W
LI
GRP
40367-68
262 Time Delay 1
∗ R
W
LI
GRP
40369-70
262 Time Delay 2
∗ R
W
LI
GRP
40371-72
362 Time Delay 1
∗ R
W
LI
GRP
40373-74
362 Time Delay 2
∗ R
W
LI
GRP
40406-07
79 First Automatic Reclose Delay
R W
LI
GRP
40408-09
79 Second Automatic Reclose Delay
R W
LI
GRP
40410-11
79 Third Automatic Reclose Delay
R W
LI
GRP
40412-13
79 Fourth Automatic Reclose Delay
R W
LI
GRP
40414-15
79 Reset Time Delay
R W
LI
GRP
40416-17
79 Reclose Fail Time Delay
R W
LI
GRP
40418-19
79 Maximum Reclose Time
R W
LI
GRP
40420
79 Sequence Control
R W
BM(16)
GRP
∗ 262 and 362 are available when style option 1 is V or W.
Global Setting Parameters
40606-07
Breaker Fail Time Delay
R W
LI
40608-09
Programmable 51 Curve Constant A
R W
FP
40610-11
Programmable 51 Curve Constant B
R W
FP
40612-13
Programmable 51 Curve Constant C
R W
FP