Figure 4-3. Panel Drilling Diagram, C1 Case
Connections
Incorrect wiring may result in damage to the relay. Be sure to check model and part number before
connecting and energizing a particular relay.
NOTE
Be sure that the relay is hard-wired to earth ground with no smaller than 12
AWG copper wire attached to the ground terminal on the rear of the unit case.
When the relay is configured in a system with other devices, it is
recommended to use a separate lead to the ground bus from each unit.