Introduction, Features, Section 1 • general information -1 – Basler Electric BE1-50/51B-244 User Manual

Page 11: Introduction -1, Features -1

Advertising
background image

9252000793 Rev C

BE1-50/51B-244 General Information

1-1

SECTION 1 • GENERAL INFORMATION

Introduction

BE1-50/51B-244 protective relays are direct replacements for Westinghouse type CO relays. The BE1-

50/51B-244 has a 5-ampere current sensing input. The BE1-50/51B-244 is provided with a case that fits

into an FT-11 cutout or an FT-21 cutout with an adapter plate (Basler P/N 9252017005). A cover is also

provided. Compatible Westinghouse model numbers are listed in Table 1-1.

Table 1-1. Westinghouse Relays Suitable for Direct Replacement

ABB Catalog Number

Curve Type

CO-2∗11∗1N

Short Time

CO-5∗11∗1N

Long Time

CO-6∗11∗1N

Definite

CO-7∗11∗1N

Moderately Inverse

CO-8∗11∗1N

Inverse

CO-9∗11∗1N

Very Inverse

CO-11∗11∗1N

Extremely Inverse

∗

Any digit covering all pickup ranges except 50 Hz models.


To replace an existing Westinghouse type CO relay, perform the following steps:

1. Select the desired relay settings on your new BE1-50/51B-244 relay.

2. Remove the existing relay and case.

3. Insert the new relay and case.

4. Install the connection plug.

5. Install the cover and secure with the captive thumbnut.

BE1-50/51B-244 relays are self-powered, compatible with 50 or 60 Hz power systems, and have three

protection elements: one time overcurrent (51) element and two instantaneous overcurrent (50) elements.

The 51 element offers timing characteristic curves similar to those used by GE IAC relays.

Features

A wide range of pickup settings and front panel selectable time characteristics permit applications

involving coordination with fuses, reclosers, cold load pickup, motor starting, and fixed time requirements.

In addition, an integrating reset function is available to simulate the disk reset of electromechanical relays.
BE1-50/51B-244 overcurrent relays have the following standard features:

•

Independent time and instantaneous elements

•

A secure method to manually trip the breaker at the relay front panel

•

Direct reading front panel controls

•

Minimum pickup setting for safety during installation

•

Time characteristics extend to a pickup multiple of 40

•

Rugged draw-out construction with steel case

•

Gravity latching targets retain indication without power

•

Built-in accuracy eliminates internal adjustments

•

Minimum transient overreach

•

Field-selectable characteristic curve selection similar to GE IAC or Westinghouse CO type curves

•

Field selectable instantaneous or integrating reset

•

Field selectable 50 or 60 Hz operation

•

Field selectable 0.0 or 0.1 second, fixed, instantaneous delay

Internal switches provide for selecting system-operating frequencies of 50 or 60 Hz, instantaneous

element delays of 0.0 or 0.1 second, characteristic curve group selection for either GE IAC or

Advertising