Basler Electric BE1-51/27R User Manual

Page 17

Advertising
background image

9137200999 Rev F

11

Table 5. Sensing Input Ranges

TAP

Range

Plate

or

Pickup

TAP Selector

Current Sensing

Terminals

A

B

C

D

E

F

G

H

I

J

ØA

ØB

ØC

N

Sensing Input Range 1, Single-Phase

*

HIGH

2.25

3.00 4.50 5.25 6.75

7.50 9.00 9.75

11.25

12.00

8,7

—

—

—

LOW

0.75

1.00 1.50 1.75 2.25

2.50 3.00 3.25

3.75

4.00

9,7

—

—

—

Sensing Input Range 1, Three-Phase

*

HIGH

2.25

3.00 4.50 5.25 6.75

7.50 9.00 9.75

11.25

12.00

8,7

14,15 17,18

—

LOW

0.75

1.00 1.50 1.75 2.25

2.50 3.00 3.25

3.75

4.00

9,7

13,15 16,18

—

Sensing Input Range 1, Two-Phase-and-Neutral

*

HIGH

2.25

3.00 4.50 5.25 6.75

7.50 9.00 9.75

11.25

12.00

8,7

—

14,15 17,18

LOW

0.75

1.00 1.50 1.75 2.25

2.50 3.00 3.25

3.75

4.00

9,7

—

13,15 16,18

Sensing Input Range 2, Three-Phase-and-Neutral

Phase

or

Neutral

0.75

1.00 1.50 1.75 2.25

2.50 3.00 3.25

3.75

4.00

8,9

13,14 15,16 17,18

Sensing Input Range 3, Three-Phase-and-Neutral

Phase

2.25

3.00 4.50 5.25 6.75

7.50 9.00 9.75

11.25

12.00

8,9

13,14 15,16

—

Neutral

0.75

1.00 1.50 1.75 2.25

2.50 3.00 3.25

3.75

4.00

—

—

—

17,18

Sensing Input Range 4, Three-Phase-and-Neutral

Phase

0.75

1.00 1.50 1.75 2.25

2.50 3.00 3.25

3.75

4.00

8,9

13,14 15,16

—

Neutral

2.25

3.00 4.50 5.25 6.75

7.50 9.00 9.75

11.25

12.00

—

—

—

17,18

Sensing Input Range 5, Three-Phase-and-Neutral

Phase or

Neutral

2.25 3.00

4.50 5.25 6.75 7.50

9.00

9.75

11.25 12.00

8,9

13,14 15,16 17,18

Sensing Input Range 6, Three-Phase-and-Neutral

Phase or

Neutral

0.15 0.20

0.30 0.35 0.45 0.50

0.60

0.65

0.75

0.80

8,9

13,14 15,16 17,18

Sensing Input Range 7, Three-Phase-and-Neutral

Phase

0.45 0.60

0.90 1.05 1.35 1.50

1.80

1.95

2.25

2.40

8,9

13,14 15,16

—

Neutral

0.15 0.20

0.30 0.35 0.45 0.50

0.60

0.65

0.75

0.80

—

—

—

17,18

Sensing Input Range 8, Three-Phase-and-Neutral

Phase or

Neutral

0.45 0.60

0.90 1.05 1.35 1.50

1.80

1.95

2.25

2.40

8,9

13,14 15,16 17,18

Sensing Input Range 9 (All Other Sensing Types)

*

HIGH

0.45 0.60

0.90 1.05 1.35 1.50

1.80

1.95

2.25

2.40

Same as Range 1

LOW

0.15 0.20

0.30 0.35 0.45 0.50

0.60

0.65

0.75

0.80

Same as Range 1

* For relays with sensing input ranges 1 or 9, connect the system wiring to the current sensing terminals
for the desired range (HIGH or LOW).