Protection and control functions, Setting groups, Differential protection – Basler Electric BE1-CDS240 General Information User Manual

Page 5: Overcurrent protection, Voltage protection, Frequency protection, Protection and control functions -3

Advertising
background image

•

Each output is programmable using BESTlogic (assign any virtual output to any physical output

relay) and can be given a user meaningful name for the variable and for each state (open and

closed) for use in reporting functions.

•

Output logic can be overridden to open, close or pulse each output contact for testing, or control

purposes.

Protection and Control Functions
Setting Groups

•

Four (4) settings groups allow adaptive relaying to be implemented to optimize the relay settings

for various operating conditions.

•

Automatic and external logic can be employed to select the active setting group.

Differential Protection

•

Three-phase percentage restrained differential protection with harmonic restraint: 87. Protection

can be set to monitor two, three, or four windings. Unused inputs can be used for overcurrent

protection.

•

Two restricted earth fault ground differential protection elements with independent ground (IG)

input (and C-phase, IG2, of Current Circuit 4): 87ND and 187ND.

•

Tap compensation for the differential protection can be automatically calculated by the relay

based upon user settings of CT ratio, MVA and kV base values.

•

Ground differential between calculated residual of any winding and the phase C current input of a

fourth and unused winding (IG2).

•

Each winding can be independently set for a phase relationship (relative to winding 1) of 0 to 360

degrees in steps of 30 degrees.

•

Each winding can be set for IEC standard transformer connections.

Overcurrent Protection

•

Instantaneous overcurrent with settable time delay for each operating quantity (A, B, C, N (using

IN or IG) and Q. Eight (8) sets Phase, Five (5) sets Neutral, Four (4) sets Negative-Sequence.

Each function is individually assignable to any of the current input circuits. Functions are: 50TP,

150TP, 250TP, 350TP, 450TP, 550TP, 650TP, 750TP, 50TN, 150TN, 250TN, 350TN, 450TN,

50TQ, 150TQ, 250TQ, and 350TQ.

•

Inverse time overcurrent functions with integrating or instantaneous reset. Four (4) for Phase, five

(5) for Neutral, and four (4) for Negative-Sequence. Each function is individually assignable to

any of the current input circuits. Functions are 51TP, 151TP, 251TP, 351TP, 51TN, 151TN,

251TN, 351TN, 451TN, 51TQ, 151TQ, 251TQ, and 351TQ.

•

Time overcurrent functions employ a dynamic integrating timing algorithm covering a range from

pickup to 40 times pickup with selectable instantaneous or integrated reset characteristics.

•

Time overcurrent curves conform to IEEE PC37.112 and include seven curves similar to

Westinghouse/ABB CO curves, five curves similar to GE IAC curves, four IEC curves, a fixed

time curve, and a user programmable curve.

•

Digital signal processing filters out unwanted harmonic components while providing fast

overcurrent response with limited transient overreach and overtravel.

Voltage Protection

•

Voltage control or restraint for 51P (51V protection)

•

One (1) volts per hertz protective element (24) provides overexcitation protection for a generator

and/or transformer.

•

Two phase (2) undervoltage elements, 27P and 127P, provide phase undervoltage protection.

•

Two phase (2) overvoltage elements, 59 and 159, provide phase overvoltage protection.

•

One (1) negative-sequence overvoltage element (47) provides protection for phase unbalance or

a reverse system phase-sequence.

•

One (1) zero sequence overvoltage element (59X) provides protection for ground faults on

ungrounded systems using calculated 3VO.

Frequency Protection

•

Six (6) over/underfrequency protection elements are provided: 81, 181, 281, 381, 481, and 581.

9365200990 Rev M

BE1-CDS240 General Information

1-3

Advertising