INTRODUCTION

This instruction manual provides information about the operation and installation of the BE1-87B Bus
Differential Relay. To accomplish this, the following information is provided:

•

General Information and Specifications

•

Controls and Indicators

•

Functional Description

•

Installation

•

Testing

WARNING!

To avoid personal injury or equipment damage, only qualified personnel should
perform the procedures in this manual.

The paddle plugs should be removed prior to performing a current circuit
insulation test. The design of the voltage-sensing circuit creates a low
resistance path to ground when the paddle plugs are installed, which results in
incorrect test results.

NOTE

Be sure that the BE1-87B is hard-wired to earth ground with no smaller than
12 AWG copper wire attached to the ground terminal on the rear of the unit
case. When the BE1-87B is configured in a system with other devices, it is
recommended to use a separate lead to the ground bus from each unit.

9282300990 Rev P

BE1-87B Introduction