1-4

BE1-27/59 General Information

9170600990 Rev L

Style Number Example

If a BE1-27/59 relay has a style number of

A3F–E1J–A0S1F, the relay has the following features:

A ------- Single-phase voltage sensing input
3 -------- Sensing input compatible with a pickup adjustment range of 55 to 160 Vac
F -------- 2 normally open output relays (one per function)
E1 ------ Definite timing for each function
J -------- Relay control power is 125 Vdc or 120 Vac, nominal
A ------- Two internally operated target indicators (one per function)
0 -------- No instantaneous functions
S ------- Push-to-energize outputs
1 -------- Two normally-open auxiliary output relays (one per function)
F -------- Semi-flush mounting case

Specifications

Electrical and physical specifications are listed in the following paragraphs.

Voltage Sensing Inputs

Nominally rated at 50/60 Hz, (120/240 V or 100/200 V) with a maximum continuous voltage rating of 360

V (120 V nominal) or 480 V (240 V nominal) at a burden less than 1 VA per phase. Frequency range is

from 40 to 70 Hz.

Undervoltage and Overvoltage Pickup Range

Pickup Range ................................... Continuously adjustable over the range of 1 to 40, 55 to 160, or 110

to 320 Vac as defined by the Style Chart. See Section 3, Functional

Description, System Voltages, for explanation of pickup ranges.

Pickup Accuracy ............................... ±2% or ±0.5 volts of the pickup setting, whichever is greater.
Dropout ............................................. ±2% of pickup.

Timing Characteristics

Instantaneous ................................... Less than 50 milliseconds for a voltage level that exceeds the pickup

setting by 5% or 1 volt, whichever is greater

Definite .............................................. Adjustable from 0.1 to 9.9 seconds, in steps of 0.1 seconds.

Accuracy is ±2% or ±50 milliseconds, whichever is greater. (A setting

of 0.0 provides instantaneous timing.)

Inverse .............................................. Inverse curve types are defined by the Style Chart and are

represented by the curves shown in Section 3, Functional

Description. Inverse time is adjustable from 01 to 99 in increments of

01. Incrementing the time dial varies the inverse curve along the Y

axis. A setting of 00 designates instantaneous timing.

Accuracy is within ±5% or 50 milliseconds (whichever is greater) of

the indicated time for any combination of the time dial setting and

pickup setting and is repeatable within ±2% or 50 ms (whichever is

greater) for any combination of time dial and tap setting. Curves

were generated with Prefault voltage at 10% greater than pickup for

the 27 curves and 10% less than pickup for the 59 curves. For

Prefault voltages that are greater in difference from the pickup

setting, the timing accuracy is ±10% or 100 ms (whichever is

greater).