Operational characteristics, Power-up, Operational characteristics -6 – Basler Electric BE1-79M User Manual

Page 30: Power-up -6, Table 3-3. wide range power supply voltage ranges, N table

Advertising
background image

3-6

BE1-79M Functional Description

9170100990 Rev N

Table 3-3. Wide Range Power Supply Voltage Ranges

Power Supply

Style Chart Identifier

Nominal Voltage

Voltage Range

Low Range

L

24 Vdc

12 to 32 Vdc ∗

Mid Range

J, K, Y

48, 125 Vdc,

120 Vac

24 to 150 Vdc,

90 to 132 Vac

High Range

Z

125, 250 Vdc,

120, 240 Vac

62 to 280 Vdc,

90 to 270 Vac

∗

14 Vdc required to start the power supply.

Relay operating power is developed by the wide range, isolated, low burden, flyback switching, solid-state

power supply. Nominal +12/–12 Vdc is delivered to the relay internal circuitry. Input (source voltage) for

the power supply is not polarity sensitive. A red LED turns

ON to indicate that the power supply is func-

tioning properly.

Operational Characteristics

Due to the microprocessor-based design of the BE1-79M Multiple Shot Reclosing Relay, many of its

operational characteristics are not apparent in the block diagram. The remaining information in this sec-

tion is focused on the software-controlled features of the relay.

Power-Up

The application of operating power results in one of four states as illustrated in Figure 3-4. Depending on

conditions and the RESET delay setting, the interval from power application to the resultant state may be

from 10 to 1000 seconds or optionally from 1 to 100 seconds. When the resultant state is reached, the

relay fail output contacts open and the RELAY FAIL LED is extinguished.