Technical data

KL1002/KS1002

KL1012/KS1012

Protection class / Installation position

IP20/ variable

Approvals

CE, cULus, ATEX, GL

Pluggable wiring

at all KSxxxx series terminals


ATEX - Special conditions

Observe the special conditions for the intended use of
Beckhoff fieldbus components in potentially explosive areas (directive 94/9/EU)!

WARNING

• The certified components are to be installed in a suitable housing that guarantees a

protection class of at least IP54 in accordance with EN 60529! The environmental
conditions during use are thereby to be taken into account!

• If the temperatures during rated operation are higher than 70°C at the feed-in points of

cables, lines or pipes, or higher than 80°C at the wire branching points, then cables must
be selected whose temperature data correspond to the actual measured temperature
values!

• Observe the permissible ambient temperature range of 0 - 55°C for the use of Beckhoff

fieldbus components in potentially explosive areas!

• Measures must be taken to protect against the rated operating voltage being exceeded by

more than 40% due to short-term interference voltages!

• The individual terminals may only be unplugged or removed from the Bus Terminal system

if the supply voltage has been switched off or if a non-explosive atmosphere is ensured!

• The connections of the certified components may only be connected or disconnected if the

supply voltage has been switched off or if a non-explosive atmosphere is ensured!

• The fuses of the KL92xx power feed terminals may only be exchanged if the supply voltage

has been switched off or if a non-explosive atmosphere is ensured!

• Address selectors and ID switches may only be adjusted if the supply voltage has been

switched off or if a non-explosive atmosphere is ensured!


Operation of the Bus Terminal System in potentially explosive areas (ATEX)!

Note

Pay also attention to the continuative documentation

Notes about operation of the Bus Terminal System in potentially explosive areas (ATEX)

that is available in the

download area

of the Beckhoff homepage

http://www.beckhoff.com

!