Terminal configuration

12

KL2502, KL2512


3.2.2 Terminal-specific register description

Process variables

R0, R1: no function

3.2.2.1 R2:

Period

In the PWM mode, the period for current operation can be specified here.
Following a power on reset, the period is taken from R35.

PWMH mode, Cnt-Cnt PWM mode:

1 digit corresponds to one 1 microsecond here
e.g.:

250 Hz => 4000 µs = 0xFA0

4 KHz => 250 µs = 0xFA


PWML mode, Frq-Cnt PWM mode, Frq-Cnt pulse mode:

1 digit corresponds to 8 microseconds
e.g.:

2 Hz

=> 500 ms = 0xF424

200Hz => 5 ms = 0x271

R3: Base frequency
In the PWM mode, the base frequency can be specified here. [R/W]

1 digit corresponds to 1 Hz

R5: PWM raw vale
The value of the processor’s PWM unit is stored in this register. The
maximum resolution for a given frequency can be computed with this
value.

R6: Diagnostic register
Not used

Manufacturer parameters

R19: Manufacturer offset B_h
16-bit signed integer
Linear equation:

Y = A_h X + B_h

This register contains the offset of the manufacturer’s linear equation. The
linear equation is activated via R32.

R20: Manufacturer scaling A_h
16-bit unsigned integer * 2

-8

This register contains the scaling value of the manufacturer‘s linear
equation. The linear equation is activated via R32.

1 corresponds to the register value 0x0100