BECKHOFF KL3041 User Manual

Page 9

Advertising
background image

Functional description

KL304x and KL305x

7


Process data

The process data that are transferred to the Bus Coupler are calculated
using the following equations:

X_adc:

Output values of the A/D converter

Y_aus: Process data to PLC
B_a,A_a:

Manufacturer gain and offset compensation (R17, R18)

B_h,A_h:

Manufacturer scaling (R19, R20)

B_w,A_w:

User scaling

(R33, R34)


a) Neither user nor manufacturer scaling are active:
Y_a = (B_a + X_adc) * A_a

(1.0)

Y_aus = Y_a

b) Manufacturer scaling active (factory setting):
Y_1 = B_h + A_h * Y_a (1.1)
Y_aus = Y_1

c) User scaling active:
Y_2 =B_w + A_w * Y_a

(1.2)

Y_aus = Y_2

d) Manufacturer and user scaling active:
Y_1 = B_h + A_h * Y_a

(1.3)

Y_2 = B_w + A_w * Y_1

(1.4)

Y_aus = Y_2

The equations of the straight line are activated via register R32.

amount rep.

user scaling

manuf. scal.

Gain, Offset adjust.

add. bits

Advertising