5. Practical example for local override operation: activation of a heating circuit

Since the focus in the event of malfunctions/failures is more on finding the source of error than on permanent availability,
targeted, limited operation of important building functions through manual interventions is required. This is where local
override operation comes in, explained here using the example of a heating circuit:

Fig. 5 In the event of a failure of the communication, the controller or the power at the Bus Coupler, local override operation can

occur through the separate power supply of the manual operating terminals.

Despite failure of the communication to the building management system or the automation device, failure of the controller
or a power failure at the Bus Coupler, the configuration shown in Fig. 5 enables local override operation through the separate
power supply of the manual operating terminals. The KM2652 relay terminal activates the pump for the heating circuit. The
analog value specification of the KM4602 specifies the valve position. Since the terminal switch positions are submitted to
the controller (and therefore the building management system), the status of the switches can be queried once the fault has
been rectified. In the event of a failure of the 230 V AC power supply within the heating circuit, local override operation can no
longer be ensured.

New Automation Technology

Beckhoff

5

For application notes see disclaimer on the last page

Substation (any automation device)

any fieldbus

KL9400

Power supply unit terminal for the K-bus
KM4602

manual operation, analog output 0...10 V
KM2652

manual operation, relay 230 V AC, 6 A

Power supply
Bus Coupler

Power supply
local override

=

Connection to BACS (Ethernet)

T

M

heating circuit

System controller

Failure

Bus Couplers and Terminals