5 routing and shielding the bus cable, 6 bus termination, 7 second address setup – Bronkhorst EtherCAT User Manual

Page 11: Outing and shielding the bus cable, Us termination, Econd, Ddress setup

Advertising
background image

BRONKHORST

®

3.5

R

OUTING AND SHIELDING THE BUS CABLE

Only use shielded cables and connection elements that also meet the requirements of category 5, class 2 according to

IEC11801, edition 2.0.

Correct shielding of the bus cable attenuates electrical interference that may occur in industrial environments. The

following measures ensure the best possible shielding:

•

Manual tighten the mounting screws on the connectors, modules, and equipotential bonding conductors.

•

Use only connectors with a metal housing or a metalized housing.

•

Connect the shielding in the connector over a wide surface area.

•

Apply the shielding of the bus cables on both ends.

•

Route signal and bus cables in separate cable ducts. Do not route them parallel to power cables (motor leads)

•

Route the signal cable and the corresponding equipotential bonding, if necessary, close to each other using

the shortest possible route.

•

Route the bus cable closely along existing grounding surfaces.

In case of fluctuations in the ground potential, a compensating current may flow via the bilaterally

connected shield that is also connected to the protective earth (PE). Make sure you supply adequate

equipotential bonding in such a case.

3.6

B

US TERMINATION

A bus terminator (e.g. using bus terminating resistors) is not necessary. If no follow-up unit is connected to an

EtherCAT unit, this is automatically detected.

3.7

S

ECOND

A

DDRESS SETUP

EtherCAT supports the use of a Second Address. Bronkhorst instruments have 3 rotary switches, with which a Second

Address can be set in the range of 0 – 4095 (0xFFF).

This value of the rotary switches will be copied to the Configured Station Alias register (address 0x0012:0x0013) at

instrument start-up.

Page 11

EtherCAT interface

9.17.063

Advertising