Delta DT3 User Manual

Page 4

Advertising
background image

4

ALARM mode)

ALARM3 DELAY: Set up Alarm 3 delay (refer to “Alarm Outputs” ) (display when OUT2 is set to
ALARM mode)

0

PV Color Change Function: Select the alarm to change PV display color. (refer to "Alarm Outputs")

OFF

OUT INVERT: Set up reverse alarm output (the last digit on the right indicates: OUT1 reverse; the
2nd last digit on the right indicates: OUT2 reverse)

0

REMOTE TYPE: Set up Remote type (display when

is set to REMO mode)

(V0:0~5V; V1:1~5V; V10:0~10V; MA0:0~20mA; MA4:4~20mA)

MA4

Select auxiliary function (refer to SV Control Mode Setting)

0

COMMUNICATION WRITE: Enable/disable communication write-in

OFF

COMMUNICATION SELECT: Select ASCII or RTU format

ASCII

COMMUNICATION NO.: Set up communication address

1

BPS: Set up baudrate

9600

LENGTH: Set up data length

7

STOP: Set up stop bit

1

PARITY: Set up parity bit

Press

to return to input type setting

E


Regulation Mode】Parameter Settings:

Display

Description

Factory Setting

AT: Auto-tuning Switch(display when setting Ctrl = PID/FUZZY, TUNE = AT, R-S=RUN)

Press

V

OFF

ST: SELF-TUNING Switch (display when setting Ctrl = PID, TUNE = ST)

OFF

PID NO.: Select the n

th

(n=0~5) PID. When set in AUTO, PID is auto-selected. (display when

setting Ctrl=PID)

0

~

PID SV NO.: Accordinig to the selection of PID No. (n=0~5), set SV value accordingly. It will allow
the system perform auto selection when it’s set to AUTO mode. (Display when Ctrl = PID/FUZZY).

0

~

P : Proportional Setting (display when setting Ctrl = PID/FUZZY and TUNE = AT)
Set P value according to the selection of PID No. (n=0~5). When P is set to AUTO, the system will
select P value accordingly.

47.6

~

I: Integral Time Setting (display when Crtl=PID/FUZZY; this parameter is set automatically when
TUNE=AT.)
Set I value according to the selection of PID No. (n=0~5). When I is set to AUTO, the system will
select I value accordingly.

260

~

D: Deviation Time SEtting: (display when Crtl=PID/FUZZY; this parameter is set automatically
when TUNE=AT.)
Set D value according to the selection of PID No. (n=0~5). When D is set to AUTO, the system will
select D value accordingly.

41

~

I OFFSET: Integral deviation setting, when Integral is not 0. (display when Crtl=PID/FUZZY; this
parameter is set automatically when TUNE=AT.)
Set IOF value according to the selection of PID No. (n=0~5). When IOF is set to AUTO, the
system will select IOF value accordingly.

0

PD OFFSET: PD offset when Integral=0 to eliminate a consistent deviation.

0

Set up Fuzzy gain value (when Ctrl=FUZZY)

4

Set up Fuzzy Deadband (when Ctrl=FUZZY)

0

OUT1 HYSTERESIS: Adjust Output 1 hysteresis (when in ON/OFF control)

0

OUT2 HYSTERESIS: Adjust Output 2 hysteresis (when in ON/OFF control)

0

OUT1 HEAT: Heating control cycle for Output 1 ( when Ctrl= PID/FUZZY/MANUAL)

OUT1 COOL: Cooling control cycle for Output 1 (when Ctrl= PID/FUZZY/MANUAL)

OUT2 HEAT: Heating control cycle for Output 2 ( when Ctrl= PID/FUZZY/MANUAL)

OUT2 COOL: Cooling control cycle for Output 2 (when Ctrl= PID/FUZZY/MANUAL)

Output

selection:

C; V; S: 5sec.

R: 20sec.

COEF: Ratio of Output 1 against Output 2 (when Ctrl= PID/FUZZY and when in dual output
control)

1.00

DEAD: Set up deadband (when Ctrl is not set to MANUAL and when in dual output)

0

PV FILTER: Set up input filter factor of PV

8

PV RANGE: Set up input filter range of PV

1.00

PV OFFSET: Adjust input compensation of PV

0.0

PV GAIN: Adjust input gain of PV

0.000

Advertising