Specifications, Electrical, Fault relay contacts – Contemporary Control Systems AI-FR Redundant Fibre Hubs User Manual
Page 2: Environmental, Data rate, Timing, Optical power budget, Dimensions, Compatibility, Shipping weight
Advertising

TD675300-0ID
2
SPECIFICATIONS
Electrical
DC
AC
Input voltage:
10–36 V
8–24 V
Input power:
4 W
4 VA
Input frequency:
N/A
47–63 Hz
Fault Relay Contacts
Max current and voltage:
500 mA
200 V
Environmental
Operating temperature:
0°C to +60°C
Storage temperature:
–40°C to +85°C
Data Rate
AI-FR hubs operate at 2.5 Mbps.
Timing
AI-FR delay time:
330 ns maximum at 2.5 Mbps
Unlatch delay time:
11.9
µ
s at 2.5 Mbps
Optical Power Budget (-FOG 850 nm at 25°C)
50/125 microns
6.6 dB
62.5/125 microns
10.4 dB
100/140 microns
15.9 dB
Dimensions
Compatibility
5.45" x 6.14" (139 mm x 156 mm)
Compliant with ANSI/ATA 878.1
Shipping Weight
Regulatory Compliance
2lbs. (.9kg)
CE Mark
CFR 47, Part 15 Class A
Mechanical