Contemporary Control Systems BACnet Cube I/O BMT-SI4 User Manual

Page 2

Advertising
background image

METZ CONNECT GmbH | Im Tal 2 | 78176 Blumberg | Germany
Phone +49 7702 533-0 | Fax +49 7702 533-433
Mounting instruction see www.metz-connect.com

2

1

6. Mounting

Power down the equipment

Mount the module on standard rail (TH35 per IEC 60715 in
junction boxes and/or on distribution panels).
Installation

Electric installation and device termination shall be done by quali-

fied persons only, by respecting all applicable

specifications and regulations.

Plug in the terminal block for bus connection

4

3

5 mm

5

6

The module can be aligned without interspace. Use the jumper plug
to connect bus and supply voltage when the modules are mounted
in series.
The maximum quantity of modules connected in line is limited

to 15 or to a maximum power consumption of 2 Amps (AC or

DC) per connection to the power supply. For any similar block of

additional modules a separate connection to the power supply is

mandatory.

Connect the cable for bus supply

Mounting in series

7. Network address and bit rate setting

Configuration Switches

Hexadecimal Switches x10, x1 define the Network-Address
(00 - F9; e.g. F9h = 15x16+9 = 249d) and Baudrate (FA – FF).

• Turn Switch x10 to E (Device is temporaryly configured as Slave)

• Turn Switch x1 to A – F to select Baudrate

• Turn Switch x10 to F, wait 1 Second

• Red and green LEDs are blinking when Baudrate ist stored in

EEPROM

• Turn Switch x10 to select Network-Address

• Turn Switch x1 to select Network-Address

Factory setting: 9600 Bit/s

Address switch x10

F

F

F

F

F

F

Address switch x1

A

B

C

D

E

F

Bit rate (Bit/s)

9600 19200 38400 57600 76800 115200

8. Software Description

Device Object

Property

Remark / Value

RW

Object_Identifier

device, default instance: 421000 + Network-Address

RW-E

Object_Name

max. 63 Bytes,
default “BMT-SI4_” + Network-Address (Hexadecimal)

RW-E

Object_Type

DEVICE (8)

R

System_Status

OPERATIONAL (0)

R

Vendor_Name

“BTR Netcom GmbH”

R

Vendor_Identifier

421

R

Model_Name

“BMT-SI4”

R

Description

max. 127 Bytes, default “”

RW-E

Location

max. 63 Bytes, default “”

RW-E

Firmware_Revision

“1.1”

R

Application_Software_Version

“1.0”

R

Protocol_Version

1

R

Protocol_Revision

12

R

Protocol_Services_Supported

read-property, write-property, subscribe-cov, who-has, who-is, device-communication-control,
reinitialize-device

R

Protocol_Object_Types_Supported

DEVICE, BINARY_INPUT, GROUP, ACCUMULATOR

R

Object_List [12]

device, binary-input 1…4, group 1…3, accumulator 1…4

R

Max_APDU_Length_Accepted

480

R

Segmentation_Supported

NO_SEGMENTATION (3)

R

APDU_Timeout

10000

R

Number_Of_APDU_Retries

3

R

Device_Address_Binding

-

R

Database_Revision

0

R

Max_Master

0…127, default 127

RW-E

Max_Info_Frames

1…255, default 1

RW-E

Active_COV_Subscriptions

max. 6 Subscriptions, for binary-input 1…4,
Confirmed / Unconfirmed, Lifetime = 0…65535 sec.

R

R: Read Property, W: Write Property, -E: Storage in EEPROM / Flash

Binary Input Object 1…4

Property

Remark / Value

RW

Object_Identifier

binary-input, instance 1 … 4

R

Object_Type

BINARY_INPUT (3)

R

Object_Name

max. 42 Bytes, default “Input 1” … “Input 4”

RW-E

Description

max. 84 Bytes, default “”

RW-E

Present_Value

INACTIVE (0) / ACTIVE (1),
writable if Out_Of_Service

R
RW

Status_Flags

IN_ALARM: 0
FAULT: 0
OVERRIDDEN: 0
OUT_OF_SERVICE:

0 / 1

R

Event_State

NORMAL (0)

R

Out_Of_Service

FALSE (0) / TRUE (1)

RW

Polarity

NORMAL (0) / REVERSE (1)

RW-E

Inactive_Text

max. 20 Bytes, default “Off”

RW-E

Active_Text

max. 20 Bytes, default “On”

RW-E

Notification_Class

Unsubscribed UnconfirmedCOVNotification
0: no COV notification, default,
1: local broadcast,
2: global broadcast

RW-E

R: Read Property, W: Write Property, -E: Storage in EEPROM / Flash