Main disconnect, Main disconnect -8, 7 main disconnect – Daktronics AF-3080-68-R,A User Manual

Page 32

Advertising
background image

Ins allation w th Only a Neutral Conductor Provided

t

i

Installations where no grounding conductor is provided must comply with article
250-32 of the National Electrical Code. If the installation in question meets all of the
requirements of article 250-32, the following guidelines must be observed:

•

Connect the grounding electrode cable at the local disconnect, never at the
display panel board.

•

A disconnect that opens all of the ungrounded phase conductors should be
used.

•

The neutral and the ground conductors should be bonded in the display
panel board.


Refer to Figure 23 below for installation details.

Figure 23: Installation with only Neutral Conductor Provided

3.7 Main

Disconnect

The National Electrical Code requires the use of a lockable power disconnect near
the sign. Provide a lockable disconnect switch (knife switch) at the sign location so
that all power lines can be completely disconnected. Use a 3-conductor disconnect to
disconnect both hot lines and the neutral. Mount the main disconnect at or near the
point of power supply connection to the sign. Provide a main disconnect for each
supply circuit to the sign.

You must locate the means of disconnection in a direct line of sight from the sign or
outline lighting that it controls. This requirement provides protection by enabling a
worker to keep the disconnecting means within view while working on the sign.

Exception: You may locate the disconnecting means that are capable of being
locked in the open position elsewhere.

Electrical Installation

3-8