Tree problems, Printer problems, Display problems – Daktronics C44 User Manual

Page 50

Advertising
background image

4-2 Maintenance

&

Troubleshooting

Tree Problems

Symptom/Condition

Possible Cause/Remedy

Tree does not light at all

•

Check power and fuse to tree

•

Check power to isolation interface

•

Check bottom left corner of screen for SLCK

•

If SLCK is there, check power to starter’s box
interface

•

Check SBI to see if 3 LED’s are lit, Trans and Rec
leads from SBI to isolation interface may be
switched

•

Check SBI Trans and Rec LED’s on isolation
interface

•

Check communications cable which transmits data
from C-44 to SLEB

Bulb in tree not lit

•

Change bulb

•

Check socket and wiring

•

Change driver board

Bulb in tree stays lit

•

Change driver board

Tree Flickers

•

Check Grounding wires in Start line Box

Printer Problems

Symptom/Condition

Possible cause/remedy

Printer not working

•

Check to see if printer is enabled at C-44

•

Check power and connectors

•

Check to see if printer select light is lit

If Log printer

•

Check communications cable which sends data to
log printer

If E.T. printer

•

Check time slip printer interface LED’s

•

Check E.T. printer data LED on isolation interface

•

Check E.T. printer fault LED on isolation interface

•

Check communications cable which sends data to
E.T. printer

Display Problems


Symptom/Condition

Possible Cause/Remedy

No display at scoreboards

•

Enabled in C-44 Configuration Menu?

•

Check power to isolation interface and displays

•

Check display transmitter board In C-44,
(Drawing A-55998) which sends data to displays
via isolation interface.

•

Check for + 12VDC on signal input of driver.

Dial-ins not showing

•

In the scoreboard enable mode, was a Y placed in
the dial-in?

•

Is the F5 key being depressed?