Flowserve Gas Barrier Control System User Manual

Page 2

Advertising
background image

2

1 Introduction

1.1 Flowserve Gas Control Systems combine flow monitoring and control elements in a

self-contained, easy-to-use unit for successful operation of pressurized or unpressurized

Flowserve Gas Seals. Control System designs range from simple standard to complex

custom including various elements and panel designs per specific gas seal and applica-

tion requirements. The purpose of this document is to provide general installation and

operation instructions while the Control System assembly drawing and Gas Seal assembly

drawing should be referenced for additional instructions or requirements.

1.2 Control System elements may include, but are not limited to, the following:

Filter/Regulator - regulates pressure and filters plant gas supply to the seal.

Pressure Indicator - indicates gas pressure supplied to the seal

Flow Indicator - indicates gas flow rate to the seal.

Check Valve - protects control system from product contamination during upset

pressure reversal.

Fixed Orifice - restricts maximum flow rate to seal in the event of seal failure.

Maintenance Bypass Valve - three-way valve used to bypass control system with

temporary, secondary gas supply for maintenance of Control System.

Pressure Alarm/Switch - electronic sensor used to alarm at low gas pressure condition.

Flow Alarm/Switch - electronic sensor used to alarm at high gas flow rate conditions.

1.3 Control Systems are used with at least the following Flowserve Gas Seal types: GF-200,

GX-200, Bufferpac 982, MD-200, ML-200, Circpac MD, GSL, GSS and GSD.

2 Before Installation

2.1 See enclosed assembly drawing for Control System component reference and special

instructions. Review instructions on the Flowserve seal assembly drawing for additional

piping recommendations. For technical assistance contact your local Flowserve Represen-

tative or Authorized Distributor.

2.2 Review the minimum/maximum system pressures that might be encountered at the

following: A. Inlet Plant Nitrogen or Air supply to control system

B. Process (seal chamber) pressure (for Plan 74 systems)

C. Vapor/liquid collection system pressure (for Plan 72 systems)

2.3 Confirm that all connecting piping, fittings, indicators and accessories are rated properly.

2.4 Confirm the hazardous area classification where the Control System is to be installed.

Confirm that the equipment ordered meets the area classification.

2.5 Inspect all connections for dirt or contamination. Blow out all tubing with instrument air

or nitrogen.

2.6 Confirm that a plug or block valve has been installed in the seal drain connection.

3 Installation

3.1 Securely mount the Control System as close as possible to the Gas Seal such that line

losses are minimal. Especially when supplying segmented ring seals, measure line losses

(pressure drop) before completing final piping to seal. Tighten all mounting hardware prior to

making any tubing connections.

The images of parts shown in these instructions may differ visually from the actual

parts due to manufacturing processes that do not affect the part function or quality.

Advertising