System Malfunctions
– continued –
LED 4 flashes slowly.
A malfunction in the level switch
has been detected.
System Malfunction 3
LED 4 flashes slowly
Fault:
The electronic circuit board of the level switch is defective
(e. g. output relay).
Remedy: Replace level switch. Restart system.
LEDs 1 to 4 flash rapidly.
A general communication
malfunction has been detected.
System Malfunction 4
LEDs flash rapidly
Fault:
No communication between bus devices possible.
Remedy: Check wiring, node ID, baud rate setting and bus cable.
Cut off power supply and restart system after 5 sec.
Fault:
No voltage across terminal 25, self-checking routine unsuccessful.
Remedy: Wire NRS 1-41 as first device in the safety chain. Wire NRS 1-41
according to wiring diagram (ensure constant voltage supply across
terminal 25). Restart system.
Fault:
Voltage across terminal 26 and/or 30.
Remedy: Do not connect these terminals.