Principles of operation: representative – Flowserve APEX 5100 Current-to-Pressure Transducers User Manual

Page 4

Advertising
background image

PS0003-CV (CVAUTO-200) 05/03

Page: 4 of 4

© 2003, Flowserve Corporation, Printed in USA

Automax Valve Automation Systems

Product Specification

The Apex 5100 I/P Module converts 4-20 mA current signals into 3-15 psi pneumatic signals needed by the
Apex 5000 Positioner. A controller card compares the input signal with an electrical pressure feedback signal
and outputs voltage, which is applied to a coil.

The coil voltage varies a magnetic field strength which influences a metallic diaphragm. This diaphragm
throttles air flow out of the positioner input chamber (supplied by the internal regulator). As voltage and field
strength increase, the diaphragm moves closer to the coil nozzle, reducing air flow and increasing positioner
input chamber pressure.

The controller circuit board features temperature compensation and input signal filtration to provide accurate
3-15 psi output signals.

Principles of Operation:

Representative:

Flowserve Corporation

1350 N. Mountain Springs Parkway

1978 Foreman Dr.

Flow Control Division

Springville, Utah 84663-3004

Cookeville, TN 38501

www.flowserve.com

Phone: 801 489 8611

Phone: 931 432 4021

AMBIENT

TEMP

SENSOR

REGULATOR

XMTR

AMP

DRIVE

AMP

INPUT

AMP

RFI

FILTER

Advertising