Flowserve DataFlo P Smart Positioner User Manual

Dataflo p smart positioner, Program mode, Functions

Advertising
background image

DataFlo P

Smart Positioner

Functions

FCD WCAIM2061-00 (Part 08987)

Program Mode

Abbreviation

Data Entry Parameter

Display

CodE

Security Code

CodE / 0000

Addr

Unit Address

Addr / 1-255

Ocur

Output Current Range

0-20 or 4-20 mA

Sdir

Setpoint Direction

riSE or FALL

SPrS

Split Range Start

0.0% to 99.9%

SPrE

Split Range End

0.1% to 100.0%

OPEn

Setpoint Ramp Time to Open

0 to 200 sec.

CLOS

Setpoint Ramp Time to Close

0 to 200 sec.

SFc

Setpoint Curve Function

Lin or FrE 1-4

dEbA

Positioner Deadband

0.1 to 10.0%

SPOS

Loss of Signal Position

0.0 to 100.0%

SPt

Loss of Signal Delay Time

0.0% to 9999 sec.

PPOS

Power On Position

0.0% to 100.0%

PPt

Power On Delay Time

0 to 9999 sec.

yA

Lower Rotation Limit

0.0 to 100.0%

yE

Upper Rotation Limit

0.0 to 100.0%

yCLS

Tight Valve Shutoff

yES or no

yOPn

Full Open Valve

yES or no

br

Brake-On Time

0.10 to 0.99 sec.

CyS

Run Time Cycles for Maintenance

CyCn

Accumulated Cycles

0–10 m cycles

AdE

Deviation Alarm Time

AHi

Upper Rotation Alarm

0.0% to 100.0%

ALo

Lower Rotation Alarm

0.0% to 100.0%

PrSt

Restore Default Parameter Values

yES or no

Worcester Actuation Systems