1 Safety Function Specification

The safety function used in LPS Actuator Series is defined

as follows:

Single acting actuator:

a. When an unsafe condition is detected in a plant by a

process sensor, the controller, via the control panel,

drives the Actuator to close the shut-down valve,

normally de-energizing a solenoid valve, and venting

air via the control system, OR

b. When an unsafe condition is detected in a plant by a

process sensor, the controller, via the control panel,

drives the Actuator to open the shut-down valve, normally

de-energizing a solenoid valve, and venting air via the

control system.

Double acting actuator:

a. When an unsafe condition is detected in a plant by a

process sensor, the controller, via the control panel,

drives the Actuator to close the shut-down valve,

depressurizing the OPEN chamber of the cylinder and

pressurizing the CLOSE chamber, OR

b. When an unsafe condition is detected in a plant by a

process sensor, the controller, via the control panel,

drives the Actuator to open the shut-down valve,

depressurizing the CLOSE chamber of the cylinder and

pressurizing the OPEN chamber.

The choice of the safety function to be implemented is

responsibility of the system integrator.

2 Configuration of the Product

The LPS Actuator Series is composed by pneumatic, single

acting (spring return) LPS-SA or double acting LPS-DA

actuators designed to operate several types of quarter-turn

valves.

The LPS-SA actuators can be assembled in the ‘fail to open’

or ‘fail to close’ configurations.

Actuator design characteristics are shown on the data plate

attached to the actuator.

The LPS-SA actuator series is available in a wide torque

range. The torque ratings of this actuator series are specified

in the document: “PRESSURE-TORQUE CHARTS LPS

SINGLE ACTING ACTUATORS” (doc. n° DUT008-LPS-SA”,

Draft Document).

The overall dimensions of the LPS-SA actuator series, their

weight, the number of available models and all the available

constructive options are listed in the documents:

“dim-data_LPS_SA_FC”, “dim-data_LPS_SA_FO”,

“Weight SA” and “Selection table” (Draft Documents).

3 Service Condition Limitations

(Limitation of Use)

The limits of operating conditions strongly depend on the

Actuator type and on materials of construction; operating

limits of temperature and pressure are indicated in the

following table:

Operating Condition

Range

Pressure

Design pressure = 12 barg

(MOP* depending on actuator size)

Tmin

- 29°C

(-60°C with special seals)

Tmax

100°C

(160°C with special seals)

*MOP = Maximum Operating Pressure, as per ISO12490.

The service condition limitations (Max Rated Pressure,

Temperature range, ... ) are included on actuator label

(see below).

Figure 1: LPS Actuator Nameplate