Installation, Operation and Maintenance Instructions

FCD WCENIM2075-00 04/07

Page 1 of 2

UltraSwitch

WGL, WPL

Description

Worcester Controls UltraSwitch™ limit switch enclosures

provide local and remote position indication for auto-

mated valves. They generally feature a Pharos™ visual

indicator with “red=closed” and “green=open” for intui-

tive local position determination. The UltraSwitch™ is

available with a number of limit switch options for remote

indication in a variety of electrical applications. They may

also be used as a junction box for direct installation of

solenoid valves.

Installation

UltraSwitches may be installed with a variety of mount-

ing hardware. For best results, specify the NAMUR shaft

option and NAMUR mounting hardware (when possible).

These options allow direct coupling to actuators without

couplings, reducing deadband.

Simply bolt bracket to actuator and UltraSwitch™

to bracket, leaving bolts finger tight. For NAMUR

applications the UltraSwitch™ shaft features an integral

alignment pin. This pin must engage the tapped hole in

your actuator shaft. For non-NAMUR applications, make

sure to properly install a coupler between UltraSwitch™

and actuator. Once the UltraSwitch™ is installed with

fasteners loosely tightened, stroke your actuator

two or three times to align the bracket. Then tighten

all fasteners.

Special Hazardous Location Instructions

UltraSwitch™ WPL and WGL series enclosures are

designed to meet NEMA 4 specifications, but may be

used in Division 2 hazardous locations when supplied

with hermetically sealed magnetic proximity switches.

For Division 2 applications utilizing hermetically sealed

switches, conduit seals are not required. See nameplate

information to verify hazardous location suitability.

UltraSwitch™ WXCL and WXML Series enclosures are

explosion proof which allows them to be used in most

Division 1 and 2 hazardous locations. You must install a

conduit sealing fitting within 18 inches of the enclosure

to meet NEC regulations. The WXCL series does feature

internal potting wells. Units provided with factory-sealed

leads do not require external sealing fittings. See IOM

WCENIM2076 for more information.

Wiring Instructions

UltraSwitch™ enclosures feature prewired switches. All

user connections are made at a numbered terminal strip.

A wiring diagram is located inside the cover and indicates

which terminal numbers correspond to switch contacts:

normally open, normally closed common, etc. Simply follow

the wiring diagram and electric code to connect switches

to your system. Note: for all magnetically tripped proximity

switches, the top switch (top and third switches for

4-switch versions) should only be used to indicate the

clockwise position: the bottom switch (second and fourth

switches for 4-switch versions) should only be used to

indicate the counterclockwise position. Any deviation from

these settings may result in erratic indication.

Solenoids may also be wired through the UltraSwitch™

enclosure. At least two auxiliary terminals are included as

standard. A ground screw is also included. Simply wire the

solenoid to auxiliary terminals, then connect power leads to

the opposite terminal side. Be sure to properly ground the

solenoid at provided ground terminal. Note: WPL series en-

closures are non-metallic: be sure to connect a ground wire

to this terminal. When two metal conduits are used with the

WPL series, an external grounding strap must be used to

connect to them.

UltraSwitch™ WXCL and WPL series enclosures include two

¾" conduit entries. WGL series enclosures include two ½"

entries. Be sure to follow the National Electric Code regula-

tions for rigid conduit, or cable systems as applicable.

CAUTION: Substitution of components may impair suitabil-

ity for Zone 2 Increased Safety.

Do not disconnect equipment unless power has been

switched off or the area is known to be non-hazardous.

Cleaning this housing by rubbing should be done in a non-

hazardous area.

DEMKO 02 ATEX 130948X

0518

II 2 G EEx me II T4-T6

-40°C ≤ Tamb ≤ +55°C, T6

-40°C ≤ Tamb ≤ +70°C, T5

-40°C ≤ Tamb ≤ +80°C, T4