10. Simultaneously press and release “SEL” and “UP” keys, then adjust

input signal to higher input value, e.g., 20 mA. Quick tap “SEL” to
lock in value.

11. Quick tap “DN” key. Display will flash between “PoC” and a number

between 0 and 5 volts.

12. Simultaneously press and release “SEL” and “UP” keys. Using the

“DN” key, adjust so shaft is full clockwise. The display should read
between .200 and .400 volts. If not, rotate potentiometer face gear
with your fingers. It is a friction fit. Quick tap “SEL” to lock in read-
ing.

13. Quick tap “DN” key. Display will flash between “PoCC” and the

feedback voltage value.

14. Simultaneously press and release “SEL” and “UP” keys. Using the

“UP” key, adjust so shaft is full counterclockwise. Quick tap “SEL”
to lock in reading.

15. Quick tap “DN” key. Display will flash between “Cyt” and a cycle

time reading.

16. Simultaneously press and release “SEL” and “UP” keys. Actuator

will automatically close, then open to measure cycle time, displaying
“PoC” at the clockwise position and “PoCC” at the counterclockwise
position.

Calibration is now complete. Press and hold “SEL” key for three seconds.
Positioner reverts to automatic control by input signal.

FCD WCAIM2060-00 Printed in USA.

(Part 08023)

For more information about

Flowserve Corporation,

visit www.flowserve.com or call

USA 1-800-225-6989.
© 2004 Flowserve Corporation,

Irving, Texas, USA. Flowserve is

a registered trademark of

Flowserve Corporation.

Worcester Actuation Systems

FLOWSERVE FLOW CONTROL
Worcester Actuation Systems
5114 Woodall Road
P.O. Box 11318
Lynchburg, VA 24506-1318
Phone: 434-528-4400
Fax: 434-845-9736

Advertising