Introduction

The Centura electric actuator is a rotary valve actuator
with output torques from 250 to 1,500 in-lbs. It has been
designed for NEMA 4, 4X, 7, 9 and can come with a
4-20 mA card for modulating service.

Storage

For short and long term storage refer to short and long
term storage conditions CE Actuator.

Maintenance

Centura Series actuators contain a permanently lubricated,
precision cut, heat treated gear train for long, reliable cycle
life. There is no need to change gear train grease; however,
should it become necessary to refill, use a multi-purpose
grease such as DuBois MPG-2.

Permanent split capacitor gearmotors have been equipped
with thermal protectors. After many operations, especially
in warm environments, the motor will heat up. To guard the
motor against overheating, the thermal cut-out blocks
power to the motor and maintains this state until the
motor’s temperature drops to a satisfactory level. This
thermal protection means that the actuator will not move
when overheated. Consideration must be given to the duty
cycle requirements of the actuator.

When replacing the cover, the machined joints must be
clean and clear of any obstructions. The integrity of the
explosion-proof rating depends on the care of these joints.

Installation

1. This section of the instruction sheet applies to the on-

off units. For instructions on Modulating units, please
see the ESP3 Electronic Servo Positioner Instructions.

2. Manually open and close valve to ensure freeness of

operation.

actuator to determine its operating range, taking note of
any explosion safety requirement. The electric actuators
are factory set for 90 degree operation.

4. Mount Accord actuator to valve with Accord

provided mounting hardware to ensure proper
alignment. Use mounting hardware that has 1 and 1/2
times bolt length engagement. (Do not use the manual
override to align actuator shaft to valve shaft, as this
could drive the actuator out of its operating range).
(

NOTE: Some valves have manual stops; remove if

appropriate or set actuator to operate within those
travel stops).

5. Care should be taken to align valve stem properly with

Accord actuator output shaft (misalignment will
cause premature failure of assembly).

6. To connect power to terminal strip of actuator, remove

the cover and locate the terminal wiring schematic
inside the cover.

7. Connect power to terminal strip according to schematic

diagram (power should be fused with a 5 amp slow-
blow fuse). The actuator should be wired and grounded
in accordance with Local and National Electrical Codes.

FCD ACAIM0075-00 (AC-75) 08/04

Page 1 of 8

Caution:

Consult factory when wiring multiple

actuators in series or parallel. Serious damage
may result. User must isolate unused winding.

8. Before replacing cover, actuate valve and check to see

if it opens and closes to preferred positions. If valve
does not perform correctly, adjust cams to set
actuator travel properly.

9. Drive actuator to desired open position. The cams are

adjusted in two ways. Simply depress the splined
“Quick-Set” cam against the spring and rotate to
desired location. Or, for very precise applications, turn
the screw inside the cam to move the tip into the leaf
of the micro switch.

CENTURA

ACE Series

3. Be sure valve and Accord actuator rotate in the same

direction and are in the same position (i.e., valve closed,
actuator closed). If not sure, electrically operate the

Caution:

To prevent ignition of hazardous atmospheres,
keep unit tight while circuits are alive. Disconnect
supply circuit before opening.

Caution:

Use heavy duty brake option ‘K’

for rubber lined butter fly valves & dampers
or applications that may back drive the unit.