Start-up, operation, alarms and testing – Flowserve SRL63-A User Manual

Page 13

Advertising
background image

13

Start-up, Operation, Alarms and Testing

– continued –

SRL 63-a

– continued –

Operation

Interval time is running.

No pilot lamp is alight.

Trouble-free operation

Interval time expires and begins
again.

Green pilot lamp "Standby" is
alight.

Standby period is running.

Perform the purging process
as shown on the PLC display.

Green pilot lamp "Standby"
flashes; yellow pilot lamp
"Bypass" is alight.

Purging time is running.
Low-level limiter is bypassed.

Purging

Val D OPEN
Val E CLOSED
Val F CLOSED

Status on the PLC display in chronological order

Purging

Val D OPEN
Val E CLOSED
Val F OPEN

Purging

Waiting for LW alarm
...37 sec.

Purging

Val D CLOSED
Val E CLOSED
Val F OPEN

Purging

Val D CLOSED
Val E OPEN
Val F OPEN

Purging

Val D OPEN
Val E OPEN
Val F CLOSED

End of purging process

Green and yellow pilot lamps
(Standby / Bypass) are extin-
guished.

Bypassing of low-level limiter is
cancelled.

Low-level limiter (LW)
Output contact: level switch
NRS 1-7 / NRS 1-9

Valve D

Valve E

Valve F

Boiler

LW

Setting shown for the
valve limit switches:
Valves in normal
operational position;
low-water level
(electrode exposed)

Advertising