Geist Watchdog 1000 Quick Start User Manual

Page 3

Advertising
background image

Watchdog 1000-Series quick-setup pack-in sheet (rev.150216A)

3

support available at www.itwatchdogs.com or www.geistglobal.com

SETUP EXAMPLES TO TEST YOUR WATCHDOG 1000-SERIES MONITORING UNIT:

Note: The following instructions assume that you have successfully connected the unit to a network, assigned it
an IP address, and have been able to bring up its Sensors page in your web browser using the “Quick-Start
Network Setup” instructions on the preceding page.)

Before the unit can log data, its real-time clock must be set to the
correct time. The System Clock settings are on the Config-Admin
page; click the

Config

tab on the left-hand side of the web page to

bring up the configuration-settings page, click the

Admin

sub-tab,

then scroll down the page until you find the time-settings block, as
shown here.

The clock can either be set manually, or it can be automatically
synced to an NTP time server. By default,

Set Clock Method

is

set to

Manual-GMT

; just fill in the

Year

,

Month

,

Day

,

Hour

,

Minutes

, and

Seconds

fields, as shown here. Note that the unit

uses a 24-hour clock format; i.e. 8AM would be represented as

08:00:00

, while 8PM would be

20:00:00

.

The unit's time is always set in GMT (Greenwich Mean Time). To convert this to your local time, set the
appropriate

GMT to local

offset (specified as + or – the appropriate amount in hours and minutes, i.e.

–05:00

for

U.S Eastern Standard Time,

+10:00

for East Australia Time, etc.) for your particular time zone. Then click

Save

Changes

, and the clock will be set. If Daylight-Saving Time is in effect in your area, be sure to add +1 to the

offset, as appropriate (i.e. use

–04:00

for U.S Eastern Daylight Time instead of

–05:00

.)

To have the unit set the time automatically via NTP, change

Set Clock Method

to

NTP

, then click

Save Changes

.

Note, however, that for this to work, you will need to have correctly set the

Gateway

and

DNS Servers

in the

Network settings block, so that the unit is able to reach the outside internet to look up the NTP server’s address
and communicate with it. If these settings are not correct, or if the network’s firewall settings are not set up to
allow the unit to access the outside internet, NTP mode will not work.

Next, the Email settings on the Config-Monitoring page need to
be configured, for the unit to be able to send alerts. If you plan to
use an external SMTP server or a “hosted” service such as Gmail
or AOL, you will need to obtain the correct SMTP settings for
your account from those services.

The unit will only work with a standard SMTP mail server. It does
not support IMAP, or the proprietary MAPI/RPC protocol used by
Microsoft Exchange and Outlook. (The unit can use an Exchange
server to send e-mails, if the Exchange server is set up to allow
SMTP connections; however, this may require some additional
configuration of the Exchange server to allow the unit to connect to it properly. Please consult the unit’s user
manual for more information on this.) Therefore, if you need to contact your service provider to get the correct
settings, you may need to explicitly mention that you are not setting up Outlook, or a browser-based e-mail client,
on a Windows or Mac computer, in order to get the correct “generic” SMTP settings from them.

To send e-mails through a Gmail account, for example, the settings would be programmed as follows:

Protocols:

ESMTP/TLS/SSL

Server:

smtp.gmail.com

Port:

587

“From” E-mail address:

complete Gmail e-mail address (i.e.

[email protected]

)

Username:

complete Gmail e-mail address (i.e.

[email protected]

)

Password:

Gmail login password

Then put the e-mail addresses you want to have e-mail alerts sent to into the

To E-mail Address

fields. Only one

address can be entered into each

To E-mail Address

field; you cannot “stack” a list of recipients, i.e.

[email protected]; [email protected]; [email protected]”, within a single

To E-mail Address

entry.

Once the correct e-mail server settings have been entered, click

Save Changes

, then click

Send Test Email

to

have the unit send a test message. If you do not receive the test message within a couple of minutes, double-check