Herrmidicool IOS Manual

I n s t a l l a t i o n , O p e r a t i o n & S e r v i c e M a n u a l

7

www.herrmidifier-hvac.com

Setpoint Parameters

Control Mode

Menu to

Adjust

Setpoint

Setpoint Range

Preset Values

1

2

3

Capacity Setpoint

•

•

•

2

10-100%

100%

Control Humidity Setpoint

•

2

20-98%

35%

Limit Humidity Setpoint

•

•

2

20-99%

75%

High Humidity Alarm

•

2

20-100%

99%

Low Humidity Alarm

•

3

10-98%

10%

Staging

•

•

•

3

1-3

1

Proportional Band

•

3

+/- 2-15%

+/- 10%

Integration Period

•

3

0-60 min

30 min

Throttling Range

•

•

3

0-25%

10%

Unit Address

•

•

•

3

0-99

01

Run Time

•

•

•

5

0-999, 999 hrs

0

Limit Input

•

•

5

Enable/Disable

Enable

Control Input

•

•

•

5

Enable/Disable

Enable