Herrtronic AD Series Installation, Operation and Service Manual

*If the conductivity of your supply

water is less than 100 micromho,
Consult Herrmidifier for specific
circuit board adjustments.
**Your actual cylinder life may be
higher or lower depending on
the exact composition of your water
supply.

Adjustable Set-point

Capacity
• Range=50-100%

•

Preset at 100%

Low Drain Threshold
• Range=50-100%

•

Preset; setting varies by unit

Cycle Time
• Range=60-300

Sec.

•

Preset; setting varies by unit

Faults

Overcurrent
•

120% of Rated Current

• System

Shutdown

Cylinder Fill
•

Fill valve open for 45 minutes without achieving capacity setpoint

• System

Shutdown

End of Cylinder Life
•

45 Minutes of operation without achieving capacity setpoint

• System

Shutdown

Conductivity*

Micromhos

(approx.)

Average Life**

Expectancy – Hrs.

(approx.)

70

2000

100

2000

135

1900

170

1800

255

1300

510

800

765

650

1020

500