K-Patents PR-21-S User Manual

Page 46

Advertising
background image

40

PR-21-S instruction manual

Figure 5.7

A slope graph

5.4.2 Diagnostic values

The values at the left of the graph are used for diagnostic purposes:

CONC

is the final concentration value including Field calibration adjustment, see

Figure 6.12.

TEMP

, see Section 5.4.3.

CCD

gives the position of the shadow edge on CCD in %.

nD

is the refractive index value n

D

from the sensor.

CALC

is the calculated concentration value without Field calibration adjustment,

Section 6.6.3

QF

or Quality Factor is a value in the range -1000–100. It measures the image

sharpness, a typical good value is 50. A QF value below 0 usually indicates
prism coating.

LED

is a measure of the amount of light from the light source in %. Should be

below 100 %.

HD TMP

= sensor head temperature, see Section 5.4.3.

HD HUM

= sensor head humidity, see Section 5.4.4.

I_SNS

value shows the current to sensor, the nominal value is 40 mA.

DTR TMP

= Indicating transmitter temperature, see Section 5.4.3.

DTR V1

gives the voltage from the power module, the nominal value is 24V.

DTR V2

gives the DC supply voltage, the nominal value is 3.3 V.

Note:

The Slope display also has a soft key

SENSOR RESTART

which can be used to

restart the current sensor (see upper left corner of the display for sensor letter)
after a sensor software update.

5.4.3 Temperature measurement

The system contains three different temperature measurements displayed to the
left of the graphs in Figure 5.6:

TEMP

is the process temperature used for automatic temperature compensation in

the Indicating transmitter (Section 6.6, “Calibrating the concentration measure-
ment”).

HD TMP

measures the temperature on the Sensor processor card PR-10100 (Fig-

ure 10.2).

DTR TMP

measures the temperature on the Motherboard of the Indicating transmit-

ter (Figure 3.6, “The Motherboard of the Indicating transmitter”).

Advertising