After concrete sets continued, Activation – single service: power/low voltage, Activation – dual service – Legrand 895DCC User Manual

Page 2

Advertising
background image

After Concrete Sets Continued:

3. Carpet: If floor covering is greater than 5/16" [7.9mm] thick, allow additional amount of the box to project above

the floor to compensate. Example: For 3/8" [9.5mm] thick carpet and padding, subtract 5/16" [7.9mm]
from 3/8" [9.5mm] and allow an additional 1/16" [1.6mm] of the box to extend above the floor surface.

4. When Installing Cat. No 895DCC on Wood Floor Covering: Cut must be square and parallel with the floor

surface. Cut top of box flush with the concrete
pour. Using a hole saw, cut a 4 3/4" [121mm]
diameter hole in the wood floor covering
concentric with the opening in the top
of the floor box. Install cover as shown below.

NOTE: A template is recommended to assure a desirable fit with the cover for thicker floor coverings. Use a 5" [127mm] diameter hole saw and remove a core from

a steel or wood sheet with the same thickness as the required projection. Lay the template over the box and make cut flush with the template’s surface.

Activation – Single Service: Power/Low Voltage:

1. Use any Walker Systems 895 or 896 (brass or plastic activation).
2. Requires 881 Floor Box Adapter, Cat. No. 881ADP.
3. Wiring capacity is noted by the first legible marking visible

in the interior of the box.

4. Wire and fasten device (if required) and cover to adapter.

5. Push adapter and cover assembly into box opening – no glue required!

Activation – Dual Service:

Low Voltage Divider – Cat. No. 881DIV

1. Divider height is determined by the first legible letter visible

in the interior of the box.

2. Using a utility knife, score the groove in the divider just above

the corresponding letter and snap apart.

3. Wiring capacity of the box is reduced by the largest number

indicated at the bottom of the divider.

4. Slide the divider in set of grooves between the center

and outer hubs.

Activation Cover – Cat. No. 895DCC (For use on 881 Floor Box):

NOTE: This cover is UL Listed for use on carpet and wood covered floors only.

1. Wire and fasten device to adapter.

2. Place duplex support plate (supplied with

divider Cat. No. 881DIV) over receptacle.

3. Attach cover over adapter with three

#8-32 x 1/2" [12.7mm] screws.

4. Remove 1/2" [12.7mm] screw plug and

pull low voltage cables through opening.

5. Insert and push adapter and cover assembly

into box opening – no glue required!

Push Downward To Engage Teeth

Walker Systems, Inc.
U.S.
1000 Innovation Drive • Williamstown, WV 26187
1-800-240-2601 • FAX 800-254-5498 • Outside U.S.: 860-233-6251
Canada:
850 Gartshore Street • Fergus, Ontario N1M 2W8
1-800-741-7957 • FAX 519-843-5980

IA0171 1101

© Copyright 2001 The Wiremold Company All Rights Reserved

Cover

Divider

Scrub Water Gasket

Adapter

Divider

Duplex Support Plate

Advertising