Box installation – concrete floor on-grade – Legrand 862 User Manual

Page 2

Advertising
background image

1. Purchase Kit No. 862KIT.

2. Attach the desired number of conduit

connectors, the mud cap, and gasket
to the 862 Series Floor Box.

3. Determine the needed height the box will sit below or

above the concrete screed line so that a flush assembly
can be achieved once the cover is attached to the box
and the finished tile or carpet flooring is in place. (Use
Table 1 and Table 2 as guides. Pay particular attention to
where the depth of cut measurement is taken – finished
vs. sub-floor.)

4. For mounting on grade, level a

concrete block taking note of the
box height with mud cap and the
desired finished (tile or carpet) floor
height above the screed line.

5. To prevent box from floating during

concrete pour, the box should be
attached to the block. One method
would be to clamp the box to the
block using wire.

6. For additional security, use a small

amount of cement around the box to
lock it in place before the final pour.

BOX INSTALLATION – CONCRETE FLOOR ON-GRADE

© Copyright 2006 Wiremold / Legrand All Rights Reserved

Wiremold / Legrand

U.S. and International:
60 Woodlawn Street • West Hartford, CT 06110
1-800-621-0049 • FAX 860-232-2062 • Outside U.S. 860-233-6251

Canada:
570 Applewood Crescent • Vaughan, Ontario L4K 4B4
1-800-723-5175 • FAX 905-738-9721

© Copyright 2006 Pass & Seymour / Legrand All Rights Reserved

Pass & Seymour / Legrand

U.S. and International:
P.O. Box 4822 • Syracuse, NY 13221-4822
1-800-611-7277

Canada:
570 Applewood Crescent • Vaughan, Ontario L4K 4B4
905-738-9195

NOTE: Knockouts can be scored with a

razor knife for easier removal.

Cover

Box

Height

Measure

for

Carpet

Measure

for Tile

Gasket
(Compressible)

DEPTH OF CUT IN FINISHED FLOOR FOR FLUSH MOUNTING IN TILE

COVER

Inches

[mm]

Fraction

895T

0.375

[9.5mm]

3/8

895TGFI

0.375

[9.5mm]

3/8

895TSP

0.312

[7.9mm]

5/16

896TCK-1/2

0.187

[4.7mm]

3/16

895TCAL

0.375

[9.5mm]

3/8

895TGFIAL

0.375

[9.5mm]

3/8

895TSPAL

0.312

[7.9mm]

5/16

896TCKAL-1/2

0.187

[4.7mm]

3/16

TABLE 1 – DEPTH OF CUT “A”

DEPTH OF CUT IN SUB-FLOOR FOR CARPET MOUNTING

(1/8" Gap for Carpet)

COVER

Inches

[mm]

Fraction

895

0.156

[3.9mm]

5/32

895GFI

0.156

[3.9mm]

5/32

895SP

0.0625

[1.5mm]

1/16

896CK-1/2

No Cut Needed

0

895TAL

0.156

[3.9mm]

5/32

895GFICAL

0.156

[3.9mm]

5/32

895SPCAL

0.0625

[1.5mm]

1/16

896CKAL-1/2

No Cut Needed

0

TABLE 2 – DEPTH OF CUT “B”

Step

Depth of Cut “A”

Step

Finished Floor

Sub Floor

Step

Depth of Cut “B”

Step

Sub Floor

43367R2 – Updated August 2006 – For latest specs visit www.wiremold.com