Legrand RC7AM2TCBK User Manual

Page 2

Advertising
background image

Disposable Plate

(removed)

Mounting Screws

Carpet/Tile

Flange

Threaded

Reducing Ring

Step 5 Cover Assembly: Catalog No. RC9CM2TC. Remove

disposable plate and replace with carpet/tile flange.
Install with 4 #6-32 x 3/8" [9.5mm] PHMS.

CAUTION: Poke-Thru device cannot be rotated in hole

after insertion into floor.

Step 6 Complete Assembly:

Catalog No. RC9AM2TC.
Insert assembly into hole.

Step 7 With the assembly installed, attach a 2" or 1 1/4"

trade size conduit fitting. If a 1 1/4" trade size
connector is used, insert the reducing ring supplied
before inserting the connector.

Step 8 Attach conduit, pull wires and the installation

is complete.

Push Down

NOTE: If Poke-Thru Device is utilized for communication

type cable, where local codes permit, conduit may
be omitted. A steel conduit fitting or a nipple that
extends a minimum distance of 1" [25mm] beyond
surface of carpet/tile flange must be utilized. Protect
wires from damage by installing a bushing suitable
for use with the type of fitting used.

Advertising